Product Features
8
AC Power Diagnostic LEDs: The three LEDs on the front panel show current power
conditions (left to right):
Protection Present (Green LED): Indicates surge-suppression components are intact and
providing full protection against spikes and surges. This LED should illuminate any time the
unit is plugged in and power is present. If the Protection Present LED does not illuminate,
some of the surge suppression components are not functioning and the unit should be
returned for repair as soon as possible. You may still use the unit; however, connected
equipment will be protected from spikes and surges at a lesser level than normal.
Fault (Red LED)*: Indicates a wiring fault has been detected. If this LED illuminates at any
time while the unit is plugged in, the fault should be repaired by a qualified electrician as
soon as possible. This LED indicates the phases are reversed, ground is missing or some
other sort of wiring error exists in the circuit the unit is plugged into. The Line Fault detector
circuitry will identify most common wiring faults, but will not necessarily detect every
possible type of fault.
Line OK (Green LED): Indicates that nominal AC power is present with no wiring faults
detected. When this LED is illuminated, AC power is safe for connected equipment.
9
NEMA 5-15R Outlets: This switch includes 12 NEMA 5-15R receptacles.
10
Circuit Breaker: If the current drawn by the equipment connected to the Smart Switch
outlets exceeds the Maximum Load Rating, the 12A thermal circuit breaker will trip to prevent
possible damage and its plunger will pop up. If this happens, disconnect excess equipment
and allow the breaker to cool at least one minute before depressing the plunger to reset the
unit.
11
AC Input: Permanently attached input cord with a NEMA 5-15P input plug.
12
Grounding Lug: Use this screw to connect your switch to ground.
* If the Line Fault (Red LED) indicator illuminates, carefully check the AC receptacle
the unit is plugged into. The receptacle must be tight and securely grounded. A loose
AC receptacle may cause the Line Fault LED to illuminate. The Red LED indicates the
presence of a wiring fault, but does not indicate the exact nature of the fault. Only
qualified electricians should make necessary outlet repairs.
If the Line Fault indicator illuminates and power is not present at the outlets,
the PDU's surge-suppression components have been compromised as a
result of surge damage. For service, contact Tripp Lite Customer Support at
www.tripplite.com/support to remedy the problem or receive instructions about
return, repair or exchange.