Setting of units:
uni
bAr = bar
PSi = PSI
MPA = MPa
Transistor function
P-n
PnP = pnp transistor output
nPn = npn transistor output
Zero-point calibration: The current pressure is transient until
Oset
the power supply is switched off and stored as the new zero
point. For safety reasons, this is limited to a value that is ±3%
of the nominal device pressure.
Application example: a system with a continuous residual pres-
sure that should be shown as zero bar.
YES = begin zero-point calibration now
no = return to menu, do not make new zero-point calibration
After the zero-point calibration, pressure up to 20 bar can be
shown as 0 bar on a 400 bar pressure switch. For that reason,
it is important to establish that there is no pressure before
starting work on a system.
Display
diS
off = 7-segment display is off
ECo = Display with brightness dimmed
rECo = Reverse eco (reverse display with brightness dimmed)
Full = Display with normal brightness
rFuL = Reverse display with normal brightness