Annex 3 : Maximum peak power calculation

Some devices will require a higher start-up power than the operating power. This specificity must be
considered.
Peak power = Equipment nominal power × start-up coefficient
See below some examples of equipment‟s showing difference between the operation power and the
minimum acceptable power for the inverter.
Equipment
FR
FR
EN
ES
IT
To identify the exact power of your equipment, please consult the manufacturer datasheets on the
device manual.
Note: Calculations have been done for mono-phase devices.
IMEON 3.6: Overload power capability at nominal
* It is necessary to take into account all technical specifications.
92
IMEON INVERTER
Operating power
Electric oven
2 500 W
Television
300 W
Portable
900 W
grinder
Circular saw
1100 W
Freezer
300 W
Single phase
1500 W
compressor
Washing
3000 W
machine
voltage (AC BACKUP) *
IMEON_installation_guide_rev.D.5
Start-up Coefficient
1
1
2,5
2,5
3,5
3,5
3,5
IMEON 9.12: Overload power capability at nominal
voltage (AC BACKUP) *
Maximum peak power
2 500 W
300 W
2250 W
2750 W
1050 W
5250 W
10 500W