3 Operation of control panel

The control panel allows to program the Ventilation Level and the Ventilation Delay using
cursors
,
and DISPLAY SELECTION.
The MANUAL VENTILATION ON/OFF pushbutton allows to activate/deactivate on manual
mode the ventilation at any moment.
The factory settings are as follows:
Parameter
Ventilation Level:
Ventilation Delay:
Post-ventilation Delay:
Alarm Level:
Alarm Delay:
4

Installation

Below picture shows the general connection outline of different components.
It is possible to connect up to 10 sensors per zone in MCO110 panel and up to 20
sensors in MCO120 panel.
Wiring: it is recommended to use cable with 1.5 mm
cable per zone must not exceed 600 m, in a lineal distribution of sensors.
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER
COsensor Control Panel
MCO110 / MCO120 / MCO120DVB
Value
Margin
50 ppm
Programmable (20  150 ppm,
on a 10 ppm increase rate)
Programmable (1  9 min, on a
4 min
1 min increase)
4 min
Fixed
200 ppm
Fixed
1 min
Fixed
Estructure per Zone
ZONE
-
+
-
-
+
+
-
-
+
+
-
-
+
+
FABRICANTS DE PRODUITS CONTRE INCENDIES
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com -
[CO]
Alarm
level
Ventilation
level
2
of minimum section. Maximum length of
ALAR.
VENT.
-
+
Ventilation
+
Alarm
CO Detectors
Note: SCO and SDN have
polarity
(CCO115 up to 15)
www.cofem.com
Alarm
Delay
Post-ventilation
Delay
Alarm
ON
Ventilation
Ventilation
OFF
Delay
Ventilation
Ventilation
ON
ON
11
Alarm
OFF
Time

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Minico mco120Minico mco120dvb

Tabla de contenido