Three-phase multifunction instrument
with 1 or 2 "Easy Connect" inputs
9. COMMUNICATION
RS485 Modbus wiring diagram:
ETHERNET
RJ45
RS485 Modbus wiring diagram with Mini Web Server:
3
RS485: Required use of Belden 9842 or Belden 3106A wire (or equivalent) for a maximum bus length of 1000 m, or Category 6 wire (FTP or
(1)
UTP) for a maximum length of 50 m
120Ω terminating resistor inside the instrument (it can be set in the SETUP menu)
(2)
Ethernet: Cat. 6 (FTP/UTP)
(3)
The "SG" terminal must never be connected to the earth
(4)
Mbus wiring diagram:
MASTER
MBUS
Communication tables
- The MODBUS and MBUS communication protocols are available on the
Technical data sheet: IDP000349EN_01
SXIIP
RT
RS-485
120 Ω
-
+
SG
(2)
(1)
SXWS10/SXWS32
RS-485
+
– SG
(1)
MBUS
A B
(5)
Non-polarized connections
A two-wire standard telephone cable (JYStY N*2*0.8 mm)
(5)
Codes: MF961ORFCDT – MF961ORFCMT
MF962ORFCDT – MF962ORFCMT
Model: NEMO 96 EC
IN
OUT
IN
RS485
MF96...
N°1
IN
OUT
RS485
MF96...
N°1
MBUS
A B
http://www.imeitaly.com
Updated: -
OUT
IN
RS485
RS485
MF96...
MF96...
N°2
IN
OUT
RS485
MF96...
N°2
MBUS
A B
site.
Created: 19/02/2021
SG
+
1
1
+
SG
OUT
RT
120 Ω
N°n
(2)
IN
OUT
RS485
RT
120 Ω
MF96...
N°n
(2)
7 / 7