Features

Circuit Breaker(s)

If the current draw of the equipment connected to your power strip exceeds your model's
Maximum Load Rating (see Specifications) for longer than a few seconds, a circuit breaker will trip
to prevent any possible damage. When a circuit breaker trips, its plunger will pop up. Remove
excess equipment and allow the breaker to cool one minute before depressing its plunger to reset
the breaker.
Grounding Lug
Use this screw (located by the power strip's receptacles) to connect your power strip to ground.
Input Receptacle (IEC Model Only)
The PDU12IEC has no power cord. Instead, it has a IEC320-C20 inlet receptacle. To connect a
PDU12IEC to utility power, use a user-supplied detachable power cord with an IEC plug on one
end and a plug appropriate to your local utility outlets on the other.

Specifications

Nominal Voltage/Frequency:
Output Power Rating (amps):
AC Receptacles:
AC Line Cord:
Circuit Breaker(s) (Resettable):
Dimensions (HxWxD, inches):
Nominal Voltage/Frequency
Output Power Rating (amps):
AC Receptacles
AC Line Cord:
Circuit Breaker(s) (Resettable)
Dimensions (HxWxD, inches):
Nominal Voltage/Frequency:
Output Power Rating (amps):
AC Receptacles:
AC Line Cord:
Circuit Breaker(s) (Resettable):
Dimensions (HxWxD, inches):
21-03-383-932120.indb 3
21-03-383-932120.indb 3
PDU1215
PDU1220
120V/50 or 60 Hz
120V/50 or 60 Hz
15 amps
20 amps
13 x NEMA 5-15R
13 x NEMA 5-15/20R
(12 rear/1 front)
(12 rear/1 front)
15', w/NEMA 5-15P plug
15', w/NEMA 5-20P plug
15 amps
20 amps
1¾ × 17¼ × 3¾
1¾ × 17¼ × 3¾
PDU121506
PDU1226
120V/50 or 60 Hz
120V/50 or 60 Hz
15 amps
20 amps
13 x NEMA 5-15R
13 x NEMA 5-15/20R
(12 rear/1 front)
(12 rear/1 front)
6', w/NEMA 5-15P plug
6', w/NEMA 5-20P plug
15 amps
20 amps
1¾ × 17¼ × 3¾
1¾ × 17¼ × 3¾
PDU12IEC
100V to 240V/50 or 60Hz
15 amps for 100V to 120V or
16 amps for 208 to 240V
4 x IEC-C13 (front),
8 x IEC-C13/2 x IEC-C19 (rear)
N/A (IEC320-C20 inlet)
2 x 16 amps
1¾ × 17¼ × 3¾
3
PDU2430
120V/50 or 60 Hz
24 amps
24 x NEMA 5-15R
(12 rear/12 front)
15', w/NEMA L5-30P plug
2 x 15 amps
1¾ × 17¼ × 3¾
PDU1220T6
120V/50 or 60 Hz
20 amps
13 x NEMA 5-15/20R
(12 rear/1 front)
6', w/NEMA L5-20P plug
20 amps
1¾ × 17¼ × 3¾
PDU1220T
120V/50 or 60 Hz
20 amps
13 x NEMA 5-15/20R
(12 rear/1 front)
15', w NEMA L5-20P plug
20 amps
1¾ × 17¼ × 3¾