IMPORTANT SAFETY INSTRUCTIONS. This manual contains information concerning the proper
installation and use of Tripp Lite's Rackmount Power Strips. SAVE THESE INSTRUCTIONS.
Do not connect your power strip to an ungrounded outlet. Do not use it with extension cords or
adapters that eliminate its connection to ground. Your power strip is designed for indoor use only.
Install it away from heat emitting devices such as radiators and heat registers. Do not install where
excessive moisture or other conductive contaminants are present. Never install electrical wiring during
a lightning storm.
Installation
1U Rackmount Installation
To Mount Unit in Rack: Put four user-supplied rackmount screws (A) through the unit's
mounting ears (B) and into the rack rails as shown. The user must determine the fitness of the
rackmount screws to hold the unit in the rack before installation.
0U Rackmount Installation
1. Reorient Mounting Ears: Unscrew the screws (A) holding the unit's mounting ears (B) to
the sides of the unit. Use the screws from Step 1 (A) to reattach the mounting ears (B) to the
unit as shown. Use only the manufacturer-supplied screws or their equivalent (#6-32, ¼" flat
head) to reattach the mounting ears.
2. Mount Unit on Outside of Rack Rails: Put four user-supplied screws (C) or similar mounting
hardware through the unit's mounting ears (B) and into the side of the rack as shown. The
user must determine the fitness of the user-supplied mounting hardware to support the unit
before mounting.
Wallmount/Under Counter Installation
Reorient the unit's mounting ears as per the 0U Rackmount Installation above, then put four
user-supplied screws or similar mounting hardware through the unit's mounting ears and into the
mounting surface. The user must determine the fitness of the user-supplied mounting hardware
to support the unit before mounting.
Features
Circuit Breaker(s)
If the current draw of the equipment connected to
your power strip exceeds your model's Maximum
Load Rating (see Specifications) for longer than a
few seconds, a circuit breaker will trip to prevent
any possible damage. When a circuit breaker trips,
its plunger will pop up. Remove excess equipment
and allow the breaker to cool one minute before
depressing its plunger to reset the breaker. Caution
(PDU2430 model only): If you depress the circuit
breaker plunger during normal operation of your
PDU, power will be interrupted to the receptacles
and connected equipment will not be protected.
Specifications
Model:
Series:
Nominal Voltage/Frequency:
Outlet Power Rating (amps):
Maximum Load Rating (amps):
AC Receptacles:
AC Line Cord:
Circuit Breaker(s) (Resettable):
Dimensions (HxWxD, inches):
Approvals:
Limited Lifetime Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for its lifetime. If the product should prove defective in material or workmanship with-
in that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite,
1111 W. 35th Street, Chicago, IL 60609. Seller will pay return shipping charges. Call Tripp Lite at (773) 869-1234 before sending any equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRAN-
TY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTEND PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED
IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long
an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights,
and you may have other rights which vary from jurisdiction to jurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes
no representation or warranty as to the suitability or fitness of these devices for any specific application.
Policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
1111 W. 35th Street Chicago, IL 60609 • Customer Support: (773) 869-1234 • www.tripplite.com • Copyright © 2003 Tripp Lite. All rights reserved.
9/24/2003
3:04 PM
PDU Rackmount
Power Strips
Designed for Mounting in 19 in. Racks
PDU1215
PDU1220
AGIP120V6IPRM
AGIP120V20RM
120V/50 or 60 Hz
120V/50 or 60 Hz
15 amps
20 amps
15 amps
20 amps
12 x NEMA 5-15R
12 x NEMA 5-15/20R
15', w/NEMA 5-15P plug
15', w/NEMA 5-20P plug
15 amps
20 amps
1¾ × 17¼ × 3 7 /8
1¾ × 17¼ × 3 7 /8
UR, cUR
UR, cUR
Page 1
Owner's Manual
Grounding Lug
Use this screw (located by the power strip's receptacles)
to connect your power strip to ground.
Input Receptacle (IEC Model Only)
The PDU12IEC has no power cord. Instead, it has
a IEC C20 input receptacle. To connect a
PDU12IEC to utility power, use a user-supplied
detachable power cord with an IEC plug on one
end and a plug appropriate to your local utility outlets
on the other.
PDU2430
AGAC120V30RM
120V/50 or 60 Hz
15 amps
24 amps
24 x NEMA 5-15R
15', w/NEMA 5-30P plug
2 x 15 amps
1¾ × 17¼ × 3 7 /8
UL, cUL
1U Rackmount Installation
0U Rackmount Installation
PDU12IEC
AGIB24016RMPDU
100V to 240V/50 or 60Hz
15 amps for 100V to 120V or 10 amps for 208 to 240V
16 amps
12 x IEC320-C13
IEC320-C20
2 x 16 amps
1¾ × 17¼ × 3 7 /8
CE