Example
L6
EP
BB
D
3
Series
L6
Construction
EP
Body
BB
SS
Switch Type
D
S
Process
3
Connection
4
Float Type and
Installation
Options
Bushing/Tees
and Bushings*
*Options that do not have ATEX, IECEx or KC
++ BSPT options not compatible with KC option
MAXIMUM PRESSURE CHART
Model Number
Float
L6EPB-B-S-3-A
Cylindrical SS
L6EPB-B-S-3-B
Polypropylene
L6EPB-B-S-3-C
Round SS
L6EPB-B-S-3-H
Round SS
L6EPB-B-S-3-O
Polypropylene
L6EPB-S-S-3-A
Cylindrical SS
L6EPB-S-S-3-C
Round SS
L6EPB-S-S-3-L
Round SS
L6EPB-S-S-3-O
Polypropylene
L6EPB-S-S-3-S
Polypropylene
INSTALLATION
Unpack switch and remove any packing material found inside lower housing or float
chamber.
Switch must be installed with body in a horizontal plane and arrow on side pointing
down.
If switch has an external float chamber (tee), connect it to vertical sections of 1˝ NPT
pipe installed outside vessel walls at appropriate levels. If unit has no external float
chamber, it must be mounted in a 1˝ NPT half coupling welded to the vessel wall.
The coupling must extend through the wall.
Inspect and clean wetted parts at regular intervals.
ELECTRICAL CONNECTIONS
Connect wire leads in accordance with local electrical codes and switch action re-
quired. N.O. contacts will close and N.C. contacts will open when liquid level causes
float to rise. They will return to "normal" condition on decreasing liquid level. Black =
common, Blue = N.O. and Red = N.C.
0
CSA
B0HB
Series L6EPB-B-D-3-0-CSA-B0HB Flotect
spherical polypropylene float, side wall mount, CSA approval, with 1-1/2" hex type
brass bushing.
Flotect
Liquid Level Switch
®
Explosion Proof
Brass
Stainless Steel
DPDT
SPDT
1" NPT
1" BSPT, M25 x 1.5 Conduit Connection ++
0
Spherical Polproplene, Side Wall Mount*
A
Cylindrical 304SS, Side Wall Mount
B
Spherical Polypropylene, Brass External Float Chamber*
C
Spherical 304SS, Side Wall Mount
H
Spherical 304SS, Brass External Float Chamber
L
Spherical 304SS, 304SS External Float Chamber
S
Spherical Polypropylene, 304SS External Float Chamber*
AT
ATEX Approval
CSA
CSA Approval*
GL
Ground Leads*
IEC
IECEx Approval
KC
Korean Certified*
MT
High Temperature*
MV
Gold Contacts
ST
Stainless Steel Tag
TBC
Terminal Block Connector
TOP
Top Mounted Float*
B0HB
1-1/2" NPT Hex Type Brass Bushing
B0H4
1-1/2" NPT Hex Type 304SS Bushing
B1HB
2" NPT Hex Type Brass Bushing
B1H4
2" NPT Hex Type 304SS Bushing
TB2BS
2" NPT Brass 250# Tee & Bushing
TB2S
2" NPT 316SS Tee & Bushing
B0HBE
1-1/2" BSPT Hex Type Brass Bushing ++
B0H4E
1-1/2" BSPT Hex Type 304SS Bushing ++
B1HBE
2" BSPT Hex Type Brass Bushing ++
B1H4E
2" BSPT Hex Type 304SS Bushing ++
TB2BSE
2" BSPT Brass 250# Tee and Bushing ++
TB2SE
2" BSPT 316SS Tee and Bushing ++
Pressure Rating
psig (kg/cm
)
2
200 (13.8)
250 (17.2)
350 (24.1)
250 (17.2)
1000 (69)
200 (13.8)
350 (24.1)
350 (24.1)
2000 (138)
2000 (138)
Liquid Level Switch, brass body, DPDT,
®
For units supplied with both internal ground and external bonding terminals, the
ground screw inside the housing must be used to ground the control. The external
bonding screw is for supplementary bonding when allowed or required by local code.
When external bonding conductor is required, conductor must be wrapped a mini-
mum of 180° about the external bonding screw. See below. Some CSA listed models
are furnished with a separate green ground wire. Such units must be equipped with
a junction box, not supplied but available on special order.
FRONT VIEW DETAIL
EU-Type Certificate IECEX and KC Installation Instructions:
Cable Connection
The cable entry device shall be certified in type of explosion protection flameproof
enclosure "d", suitable for conditions of use and correctly installed. For Ta ≥ 65°C
cable and cable gland rated ≥ 90°C shall be used.
Conduit Connection
An Ex d certified sealing device such as a conduit seal with setting compound shall
be provided immediately to the entrance of the valve housing. For Ta ≥ 65°C wiring
and setting compound, in the conduit seal, rated ≥ 90°C shall be used.
Attention: Units without the
"AT" suffix are not Directive
2014/34/EU (ATEX) compli-
ant. These units are not in-
tended for use in potentially
hazardous atmospheres in
the EU. These units may be
CE marked for other Direc-
tives of the EU.
LOCKWASHER
SCREW
CLAMP
SIDE VIEW DETAIL
CONDUCTOR