TECHNICAL DATA

RD PRO - Power supply from above
kWh
F
N
Id
User's system
- Rated voltage Vn: 230Vac phase/neutral TT and TN
- Operating voltage: from 0.85 to 1.1 Vn
- Maximum reset duration: 2 minutes
- Minimum interval between two consecutive closings: 3 minutes
- Insulation voltage towards earth: 2500V
- Power absorbed with the differential switch closed: 0 VA
- Power absorbed with RESTART blocked: 3 VA
- Power absorbed with RESTART waiting: 3 VA
- Use temperature: from - 5°C to + 40°C
- Auxiliary contact:
- rated voltage: 230V (A.C./D.C.)
- maximum current: 100mA cosϕ=1 (A.C./D.C.)
- minimum operating current: 0,6mA
I
- type: Photomos
- terminal capacity: 2,5 mm
The technical and electrical properties are the same as for the associated
switch.
F

INSTALLATION DIAGRAMS

LINE
D
R
LOAD
2
RD PRO - Power supply from below
User's system
Id
F
N
kWh
24
LINE
R
D
LOAD