Connecting The Refrigerant Piping; Precautions When Connecting The Refrigerant Piping; Guidelines When Connecting The Refrigerant Piping; Pipe Bending Guidelines - Daikin RXS50K2V1B Manual De Instalación

Ocultar thumbs Ver también para RXS50K2V1B:
Tabla de contenido

Publicidad

5 Installation
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable's ends. Tighten those ends.
5.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING
5.3.1
Precautions when connecting the
refrigerant piping
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R410A unit to guarantee
its lifetime. The drying material may dissolve and
damage the system.
NOTICE
Take the following precautions on refrigerant piping into
account:
▪ Avoid anything but the designated refrigerant to get
mixed into the refrigerant cycle (e.g. air).
▪ Only use R410A when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that
are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials
(e.g. mineral oils and moisture) from mixing into the
system.
▪ Install the piping so that the flare is NOT subjected to
mechanical stress
▪ Protect the piping as described in the following table to
prevent dirt, liquid or dust from entering the piping.
▪ Use caution when passing copper tubes through walls
(see figure below).
Unit
Installation period
Outdoor unit
>1 month
<1 month
Indoor unit
Regardless of the
period
INFORMATION
Do NOT open the refrigerant stop valve before checking
the refrigerant piping. When you need to charge additional
refrigerant it is recommended to open the refrigerant stop
valve after charging.
Installation manual
12
5.3.2
Take the following guidelines into account when connecting pipes:
▪ Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before
tightening firmly.
▪ Always use two wrenches together when loosening a flare nut.
▪ Always use a spanner and torque wrench together to tighten the
flare nut when connecting the piping. This to prevent nut cracking
and leaks.
a
d
Piping size
5.3.3
Use a pipe bender for bending. All pipe bends should be as gentle
as possible (bending radius should be 30~40 mm or larger).
5.3.4
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing downward so that the
Protection method
Pinch the pipe
a
Pinch or tape the pipe
3 Remove the flare nut from the stop valve and put the flare nut
4 Flare the pipe. Set exactly at the position as shown in the
Guidelines when connecting the
refrigerant piping
b
c
a
Torque wrench
b
Spanner
c
Piping union
d
Flare nut
Tightening
(mm)
torque (N•m)
dimensions (A)
Ø6.4
14.2~17.2
Ø9.5
32.7~39.9
Ø12.7
49.5~60.3
Ø15.9
61.8~75.4

Pipe bending guidelines

To flare the pipe end

CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
chips do not enter the pipe.
b
a
Cut exactly at right angles.
b
Remove burrs.
on the pipe.
following illustration.
A
RXS50+60 + RX50+60 + ARXS50~71
Flare
Flare shape
(mm)
(mm)
90° ±2
8.7~9.1
A
16.2~16.6
R=0.4~0.8
19.3~19.7
R410A split series
3P360062-1H – 2016.09

Publicidad

Tabla de contenido
loading

Tabla de contenido