To Drill A Wall Hole; To Remove The Pipe Port Cover; To Provide Drainage; General Guidelines - Daikin FTXP50M2V1B Manual De Instalación

Ocultar thumbs Ver también para FTXP50M2V1B:
Tabla de contenido

Publicidad

Class 50~71:
a
122
d
a
e
56.5
170
a
Recommended mounting plate fixing spots
b
Pocket for the pipe port cover
c
Tabs for placing a spirit level
d
Through-the-wall hole Ø65 mm
e
Drain hose position
f
Position for the tape measure at symbol " "
g
Gas pipe end
h
Liquid pipe end
5.2.2

To drill a wall hole

CAUTION
For walls containing a metal frame or a metal board, use a
wall embedded pipe and wall cover in the feed-through
hole to prevent possible heat, electrical shock, or fire.
NOTICE
Be sure to seal the gaps around the pipes with sealing
material (field supply), in order to prevent water leakage.
1 Bore a 65  mm large feed-through hole in the wall with a
downward slope towards the outside.
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.
a b
c
a
Wall embedded pipe
b
Putty
c
Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do
NOT forget to seal the gap with putty.
5.2.3

To remove the pipe port cover

To connect the piping on right-side, right-bottom, left-side or left-
bottom, the pipe port cover MUST be removed.
1 Cut off the pipe port cover from inside the front grille using a
coping saw.
FTXP50~71M2V1B + FTXF20~71A2V1B
Daikin room air conditioner
3P512025-7H – 2018.09
b
c
PIPING HOLE
PIPING HOLE
h
CENTER:170mm
CENTER:170mm
TO THE LEFT
TO THE LEFT
475
a
c
PIPING HOLE
PIPING HOLE
CENTER:170mm
CENTER:170mm
TO THE LEFT
TO THE LEFT
g
f
60
404
990
2 Remove any burrs along the cut section using a half round
needle file.
NOTICE
Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.
5.2.4

To provide drainage

Make sure condensation water can be evacuated properly. This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. If drain hose extension or embedded drain piping is
required, use appropriate parts that match the hose front end.
5 Installation
a
121.5
d
e
A
A
a
170
56.5
(mm)
Installation manual
9