1.3
Intended Use
The electric heat exchanger is exclusively designed for heating bathwater with acti-
vated recirculating or filter pump.
Any other mode of application is not regarded as intended use. The manufacturer is
not liable for any resulting damage.
Other uses are only possible upon agreement with and approval by the manufacturer.
Important!
The intended use also includes
– observance of all pieces of information in the installation instructions and
– execution of inspection and maintenance activities.
Maximum permissible operational overpressure of 300 kPa (3 bar) must not be
exceeded.
Minimum permissible operational overpressure of 10 kPa (0.1 bar) must be
achieved.
The minimum throughput is 1000 l/h.
Water with the following values may only be used
EWT 60/20/30/25/35
Chloride content
Free chlorine
pH value
EWT 60 TD/TDS
Chloride content
Free chlorine
pH value
salt content
Retrofits and changes in the heat exchanger are prohibited for safety reasons. For
safety reasons, maintenance and repair activities in piping and electrical installation
are only to be executed by specialist personnel.
max. 500 mg/l
max. 1.3 mg/l
6,8 – 8,2
max. 3000 mg/l
unlimited
6,8 – 8,2
max. 3,5%
Safety
29