4.
For fixtures with asymmetric light patterns, locate the
word "streetside" on the overhang plate and rotate the
fixture on the pole such that the word "streetside" is
facing the street.
5.
Secure the fixture to the pole top by tightening the
three-square head bolt using 9/16" socket and torque
wrench in the fixture base. Recommended tightening
torque: 120-140 in-lbs.
6.
Reattach bottom cover plate to fixture base and secure
with two cover retaining screws.
7 .
The fixture is now ready to energize.
Standard Fixture with Lens Installation
Tools Required:
5/16" Nut driver, 1/4" nut driver, #10 Phillips head
screwdriver, 9/16" socket, Torque wrench.
1.
Loosen the captive cover retaining screw using 5/16"
driver or loosen spring latches and open the hinged top
cover of the fixture. (Figure 3.)
Wiring
compartment
Figure 3.
Caution: Secure the fixture from falling, rotating, and
swinging freely due to weight of the LED driver, surge
module, and/or transformer attached inside of hinged top
cover as it is open. Always maintain contact.
Cupola
Screws (3)
Captive Cover
Retaining Screw
(1) or Spring
Latches
Bottom Cover
Plate
Fixture Base
COOPER LIGHTING SOLUTIONS
Installation Instructions – LXF/LXT
2.
Gently lift the right-side panel out of the slotted corner
posts. (Figure 4.)
Hinged Top Cover
LED Assembly
Figure 4.
3.
Reach bottom cover plate from open right-side of the
fixture. (Figure 4.)
4.
Unscrew two screws using 5/16" driver or #10 Phillips
head screwdriver from bottom cover plate at fixture
base. (Figure 1.) Remove bottom cover plate to gain
access to the wiring compartment.
5.
Pull electrical service leads through the pole with
sufficient length to reach through and into the wiring
compartment of the fixture. The service leads should
pass through the large, circular openings in the
mounting plate to avoid cutting or pinching the leads.
6.
Connect service leads to the appropriate position with
the terminal block. (Figure 2.)
a.
Three-terminal block (2-wire service): Connect
line service lead to terminal that is connected to black
factory-installed wire. Connect neutral service wire to
terminal that is connected to white factory-installed
wire.
b.
Three-terminal block (3-wire service, 2 lines, 1
ground): Connect 1-line service lead to terminal that is
connected to black factory-installed wire. Connect other
line service lead to terminal that is connected to white
factory-installed wire. Connect ground service lead to
terminal that is connected to green factory-installed
wire.
IB516007EN
Lens Panel
Bottom Cover Plate
Installation instructions
3