Mounting Information - D+H CDC-0252-1-TMS+ Manual Original

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Stroke limiting with magnets
When using two CDC-0252-1-TMS+ on one window , both drives must be electrically connected
in order to set the stroke , although only one drive needs to be switched to the stroke learning
mode with the magnet .
1
Close drive.
Minimum sash height/ -width
x
The details apply to a
non-rotational installation of the drive!
(Window inwards opening)
Standard chain:
Minimum size (mm) = Stroke (mm) x 3.9
Maximum stroke : 800 mm
8/20
CDC-0252-1-TMS+
2
Voltage must continue to
be applied to the drive when
moving in the "CLOSE"
direction. Hold the magnet next
to the drive as shown in the
diagramme (2 sec.) until you hear
a pulsating ton > The drive is now
in learning mode. The magnet can
now be removed and the drive no
longer has to be under voltage.
appr. 2 sec.

Mounting information

x
- Mount the drives whilst under zero stress. With
that, an even load distribution is provided by all
the drive chains.
- At vertical active pulling application (e.g. for a
skylight) the forces must be rearranged by
software SCS.
- If after mounting, the distance X is greater than 23
mm, null balance with software SCS is neccesary.
Closure Ranges will shift in relation to new zero
point.
English
3
"OPEN" until you reach the
required stroke.
If the stroke is set incorrectly,
the procedure is accidentally
interrupted or the drive
continues to the full stroke
length, please return to point 1
and start again.
learning mode
99.827.61 1.0/01/18
Allow the drive to run
STOP
≥ 23 mm ?
X

Publicidad

Tabla de contenido
loading