Sivoia QED
Installation Instructions
Please Leave for Occupant
Please read before installing.
Important Notes
1. All wiring must be in accordance with national and local
electrical codes.
2. This panel must be installed by a qualified electrician.
3. Ambient operating temperature: 32 – 104 °F (0 – 40 °C),
0 – 90% humidity, non-condensing. Indoor use only.
4. SEPARATE OVER CURRENT PROTECTION IS
REQUIRED TO BE PROVIDED IN ACCORDANCE
WITH THE CANADIAN ELECTRICAL CODE, PART I.
Installation
1. Mount Power Panel using one of the following
methods (mounting hardware is not provided):
a. Surface Mount - Using the pattern of the keyholes
on the rear of the Power Panel, install three bolts
into the wall, but leave a 1/4 in. (6 mm) gap between
the wall and the head of the bolt (use bolts rated for
a 50 lb. (23 kg) load, 1/4 in. (M6) bolts (recommend-
ed). See Figure 1. Hang the Power Panel on the
bolts and tighten securely.
b. Recess Mount - Install a 2 in. x 4 in. (50 mm x 100
mm) board as a bottom support between studs.
Using four screws, fasten the Power Panel to the
stud on the right and bottom support using the four
mounting holes provided. See Figure 1.
Note - This equipment is air-cooled. Mount in a location
where the vented cover will not be blocked.
Danger - Locate and lock supply breaker in the
OFF position before wiring to the terminal blocks.
Failing to do so could cause death or serious injury.
2. Run 120 V~ power wiring into the Power Panel.
Remove one of the knock-out tabs on the top left side of
the enclosure near the terminal blocks. Insert strain relief
into the knock-out hole. Run the power wire through the
strain relief to the terminal blocks at the top left side of
the enclosure. Note: Maximum of 1 Sivoia Panel per 15
Amp High Mag Breaker. Maximum of 2 Sivoia Panels
per 20 Amp High Mag Breaker. Maximum feed breaker
size of 30 Amps. (See Figure 2). Each terminal block will
accept one 10-18 AWG wire. Tighten terminal blocks to
3.5 to 5 in-lbs. (0.4 – 0.6 N•m) Do not overtighten.
3. Run Power Supply/Comm Link wiring into the
panel. Remove as many knock-outs tabs as necessary
from the left side of the enclosure and insert strain reliefs. Run
the low-voltage Power Supply/Comm Link wiring from
the Sivoia QED Electronic Drive Unit (EDU) through the
strain reliefs to the terminal blocks on the left side of
the enclosure. (See Figure 2.) Note: Each Electronic
Drive Unit (EDU) must be properly earth grounded. The
maximum shade size limitation on each output is a sin-
gle EDU with up to 100 ft
(225 ft
(20.9 m
) for high torque Electronic Drive Unit).
2
2
®
(9.29 m
) of shade fabric
2
2
SVQ-10-PNL
Power Panel
~
120 V
60 Hz 8 A maximum total current
Figure 1: Mounting Diagram and
Dimensions
16 in.
(406 mm)
10-3/8 in.
(264 mm)
17-1/2 in.
(445 mm)
2 in. x 4 in.
(50 mm x 100 mm
Bottom Support)
4. Run communication wiring between Power Panels.
If more than one Power Panel is in the system, you will
need to connect the Communications Links together.
Run communications wire, four conductor foil shielded
with drain, between each Inter-panel connection
terminal block. Refer to Figure 3 for wiring details.
5. Install cover. Ensure that the vents are on the left side
of the cover. Tighten screws to 20 in-lbs (2.3 N•m).
English
4-3/4 in.
(121 mm)
14-3/4 in.
(375 mm)
6 in.
(152 mm)
1-3/4 in.
(45 mm)
1-3/16 in.
(30 mm)