Electrical installation • Instalación eléctrica
Installation electrique • Elektrische Installation
C
H
K
K
H
G
K
H
10
F
0.8
0.7
0.6
0.2
0.1
C
E
0.0
F
0.8
0.7
0.6
G
C
E
A
B
E
F
D
Vac - voltages
normally open
common
normally closed
PE
Earth/Ground
Neutral
N
L
Phase
24 Vdc - voltage
normally open
common
normally closed
+24 Vdc (0V)
±24V
±24V
0V (+24 Vdc)
english
• Lift off domed cover (A) after remo-
ving the 4 screws (B).
• Take power supply board (C) out of
the domed cover (A) after removing
the screw (D).
• Guide cables for power supply (E)
and potential-free contact (F)
through screwed cable fittings.
• Terminals
Check type plate
permissible mains voltage and
ensure conformity!
Vac power supply
24 Vdc power supply
In the case of 24 Vdc operation, do not
connect +24 Vdc to frame because
the internal housing potential of the
device is negative.
• Connect potential-free contact (F)
to terminals 0.6 - 0.7 (fail safe) or
0.7 - 0.8 (open during malfunction).
• Pull cable (E + F) tight and screw
down cable fittings.
• Screw power supply board (G) with
screw (D) into domed cover (A)
• Plug ribbon cable (H) into control
PCB (K)
• If the individual wires have not been
screwed into the plug, they should
be attached as follows:
1.0 = brown
1.1 = blue
2.0 = black
• Put on top of cover (A) and tighten
the 4 screws (B)
Please note:
The power supply board (C) is in a
reverse position (upside down) in the
domed cover (A).
During no-load operation, a voltage of
up to 36 Vdc may be measured at
terminals 1.0 and 1.1(plug ribbon ca-
ble (H)).
Please ensure that the installation is
carried out according to the valid re-
gulations.