INSTALLATION INSTRUCTIONS
E-FFC05 and E-FFC08 Series
½"
ADJUSTABLE FITTER MOUNTING
(Requires use of E-ACW-FFC Accessory)
NOTE: Fixture can be mounted to any metal ½" NPSM threaded
mounting (supplied by others).
NOTE: When mounting the fixture in an inverted position (½" fitter
above fixture), mount fixture to a watertight junction box and cover.
Also, caulk the conduit openings, around the junction box cover, and
the wire entry end of the ½" fitter with a high grade caulking material,
such as silicone rubber, to ensure water does not enter fixture through
½" fitter.
1.
Route fixture ground wire (green), common wire (white) and
voltage wire (black) through upper and lower sections of ½" fitter.
Wires should exit threaded base of fitter. See Figure 2.
2.
Attach ½" fitter to housing with (4) supplied Allen bolts and Allen
wrench. Tighten bolts to 72 in-lbs (8.1 N•m).
3.
Route fixture leads through hole in mount.
4.
Thread mounting onto end of fitter on fixture and secure with
locknut. Using thread sealant on the threads will ensure a
watertight seal.
Wire as indicated in Electrical Connections section.
5.
6.
Aim fixture by loosening screw on knuckle of fitter and rotating
fixture to desired tilt angle. Re-tighten screw.
FIGURE 2
Lower
Fitter
Upper
Fitter
(4) Allen
Bolts
½"
Locknut
www.e-conolight.com
|
Document:
LPN00670X0002A0_A
Created By:
TMT

ELECTRICAL CONNECTIONS

Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
FCC NOTICE Class B
CAUTION: Changes or modifications not expressly approved could
void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Changes or modifications not expressly approved could void your
authority to use this equipment.
This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following
measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.
CAN ICES-005 (B)/NMB-005 (B)
888.243.9445
|
FAX: 262.504.5409
Date
10-30-2019
ECO#
011204