Operating Instructions and Parts Manual
Installation
1. Install pump in a sump pit with
minimum size as shown in Figure 1.
Construct sump pit of tile, concrete,
steel or plastic.
Check
Grounded
Valve
Outlet
Inlet
Pipe
Figure 1
14 in. Dia.Min.
2. The unit should be located and
rest on a solid, level foundation.
Do not place pump directly on clay,
earth, gravel or sandy surface. These
surfaces contain small stones, gravel,
sand, etc. that may clog or damage
the pump and cause pump failure.
Flood risk. If
fl exible discharge
hose is used, make sure pump is secured
in sump pit to prevent movement.
Failure to secure pump could allow pump
movement and switch interference and
prevent pump from starting or stopping.
3. A check valve is required in the
discharge line to prevent back-flow
when the pump shuts off. It is best
to install the check-valve directly to
the pump discharge. Thread a check
valve into the pump discharge.
4. Connect 1-1/4 in. or 1-1/2 in. rigid
pipe to rubber boot on check valve.
(Reverse boot for 1-1/2 in. diameter
pipe.) Tighten hose clamps.
Support pump
and piping when
assembling and after installation. Failure
to do so could cause piping to break,
pump to fail, etc. which could result in
property damage and/or personal injury.
5. Protect electrical cord from sharp
objects, hot surfaces, oil and
chemicals. Avoid kinking the cord and
replace damaged cords immediately.
Make sure there is
adequate room for
the fl oat switch to move freely during
operation (see Figure 2).
6. A sump pit cover must be installed
to prevent debris from clogging or
damaging the pump.
www.blueangelpumps.com
Place pump
where the
fl oat will not
be obstructed
A freely
moving fl oat
ensures that
the pump will
perform properly.
24 in.
NOTICE: An obstructed
Min.
fl oat will cause the pump to fail.
Figure 2: BCST and BSPT series
7. Position pump switch AWAY from
the inlet so switch is clear from
Inlet
incoming water (See Figure 3).
Screen
INCOMING
WATER
INLET PIPE
CHECK VALVE
Figure 3 - BCAP and BCSC Series
Operation
the power source before
attempting to install, service,
relocate or maintain the pump.
Never touch sump pump, pump motor,
water or discharge piping when pump is
connected to electrical power. Never handle
a pump or pump motor with wet hands or
when standing on wet or damp surface or
in water. Fatal electrical shock could occur.
1. A ground fault circuit interrupter
(GFCI) is required (See Figure 3).
is supplied with a grounding conductor
and grounding type attachment plug.
Use a grounded receptacle to reduce the
risk of fatal electrical shock.
Never cut off the round grounding prong.
Cutting the cord or plug will void the
warranty and make the pump inoperable.
2. This pump is only for use on 120 Volt
(single-phase), 60 Hz, 15 amp service and
BCAP, BCSC, BCSM, BCST, BSPM, BSPT Series
DO NOT USE AN EXTENSION CORD
Figure 4
3. Insert the pump power cord plug
4. Fill sump with water. The pump will
DISCHARGE PIPE
GFCI PROTECTED
OUTLET
is submerged in water. Dry running
ON
8"
@
causes pump failure.
SWITCH
5. While the pump is draining the pit,
OFF
@
APPROX. 3"
6. If pump discharge line is exposed to
Always
disconnect
NOTE: The motor is equipped with an
automatic reset thermal protector.
(BCAP and BCSC Series only)
Solid-state water sensor modes of operation:
Risk of electrical
shock! This pump
Figure 5 - Solid state water sensor
2
is equipped with a 3-conductor cord and
3-prong, grounding type plug. BSPM
and BCSM pumps must be connected
to a control system for automatic
operation. For all other models, insert
the switch cord plug directly into a GFCI
protected 120 volt outlet.
Grounding
Grounded
Blade
Outlet
TEST
Power
Cord
Switch
Cord
directly into the back of the switch
cord plug, (See Figures 4 and 5).
start automatically when the water
has filled the sump to a depth of
approximately 13 in. (8 in. for BCAP
and BCSC Series). The pump will stop
when the water depth is approximately
7 in. (approximately 3 in. for BCAP and
BCSC Series). The pump will recycle
thereafter as required.
Do not operate the
pump unless it
verify that the discharge piping is
carrying the water to a point several
feet away from the foundation.
freezing temperature, the exposed line
must be pitched to drain. Trapped water
will freeze and damage the pump.
• Sump pump will turn on when water is
about 1.5 in. from the top of the switch.
TEST
RESET
Keep sensor
face free
of foreign
material
RESET