EXAMPLE OF CONNECTION FOR A DLM ROOM WITH LMTI-100 AND LMEQ-41
Corner Mount
Sensor
(LMRJ or Cat5e/Cat6 cable)
Are...
Create Admin Password
Initialize System
LMEQ-41
Do not connect to
DLM local Bus (IRB)
RJ-45 Connector
4" Square Junction Box,
Single Gang Mud Ring
(Low-voltage bracket can be
used if application allows)
UPGRADING THE LMEQ-41 VIA THE LMTI-100
The LMTI-100 contains an additional port next to the PoE ports,
labeled Class 2 Ethernet Diganostic Port. This port is used for
connection to LMCS-100 software, allowing the LMEQ-41 firmware
to be updated. For details, see the LMCS-100 User Manual.
LMTI-100-120
DLM Touchscreen Injector
120VAC, 50/60HZ, Class 2 Output: 44-50VDC, 280mA
Converts DLM communication to touchscreen platform
PoE Connectors
Ethernet Connector
26513r1
Ceiling Mount
Sensor
Unswitched
Line
PoE Connection
Voltage
LMTI-100
PoE/PoE+
Ethernet Cable
Cat 5e cables
*Use flat-head screws provided – US 6-32 x 0.75"
FCC Class A
CAN ICES-3(A)/NMB-3(A)
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
UL60950 POE Compliant
Indoor Use Only
Made In China
APPLIANCE
CONTROL
88T9
E101196
www.legrand.us/wattstopper
Line
DLM Local Network
Voltage
Low Voltage
LMRJ Cables
Room
Controller
Deep J-Box
LMTI-100-xxx
Mounted above the ceiling
Connects via DLM room's local
Bus (IRB) Cat 5e cables. Each
LMTI-100-xxx can power
up to two LMEQ-41 touchscreens
Screws*
NOTE: Max recommended cable
lengths for both IRB connection
to the LMTI and POE from the
LMTI to the LMEQ:
IRB to LMTI: IRB standard-
150' between devices,
up to 1,000' total
PoE to LMEQ-41: Up to 300'
LMEQ-41
The configuration button (Config) allows access to Wattstopper's
patented Push n' Learn™ technology to change binding
relationships between sensors, switches and loads.
2
Line Voltage
Load
Examples
(any relay)
Switched
A
etc.
Switched with
0-10 Volt control
B
B
Dimming Ballast
LED Driver, etc.
0–10V Dimming
DLM Local Bus (IRB)
CAT 5E Cable
CONFIG BUTTON
Lighting Management
IRB Network Ports
Configure
Button