IMPORTANT: Provide each unit with a single-phase AC un-switched power supply from a circuit used for normal lighting.
"UVOLT" product versions operate from 120 volts through 347 volts. All other versions operate from 120 volts through 277 volts.
PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
NOTE: The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the battery
is connected longer than 24 hours without continuous AC power provided. See also "Important Battery Information", page 4.
NOTE: The maximum mounting height of ELM2L from ground is 11.7 feet, to meet the minimum illumination requirements of NFPA 101
(current Life Safety Code).
NOTE: Do not connect battery or power unit until remote units (if applicable) are fully connected and wires are isolated from other potentials
(i.e. remote wires shall be isolated from earth ground).
JUNCTION BOX MOUNTING
-Some details shown below may vary-
On the mounting plate, remove the
1
round center knockout and the
desired pair of keyhole knockouts
from junction box.
Mounting Plate:
CONDUIT SURFACE MOUNTING
NOTE: to avoid interference with components in the housing, use the most compact wire connectors appropriate to the wire gauge.
At upper center of the mounting plate,
1
remove
the
conduit
knockout. Remove required keyhole
slots from mounting plate to support
the product on the given wall type.
Figure-2
Figure-3
INSTALLATION and WIRING
Locate three or two-wire input harness,
2
make the branch circuit connection with
a UL Listed connector. NOTE: Unused
input wire should be capped. Tuck
excess wires into the junction box and
push
the
mounting plate knockout ensuring that
enough is sticking out to make the
connection
Assembly" step 5, page 3.
Junction boxes accommodated:
See Wiring Diagram, page 3. Make
2
connection
code-approved wire connections to the
branch circuit and remote lamps (if
applicable). Dress wires into slots so
that the connectors are secured as
shown in Figure 2 or Figure 3.
Secure wire connectors near the
centre or near the upper latches
Use washer(s), like (Grainger #4DAX6),
between conduit fitting and rear housing, if
conduit fitting interferes with battery. The
purpose of the washer is to have as few
threads inside of the housing as possible.
connector
through
the
as
shown
in
"Final
4" Square
4" Octagon
3-1/2" Round or Octagon
Single Gang Box
Orient conduit fitting so that
all portions of it clear the
edge of the knockout
Washer
Battery
Mount the mounting plate to the
3
junction box. Prevent the wires from
pinching between the plate and wall.
NOTE: Do not overtighten the
mounting screws. The backplate
must remain flat for the housing
snap features to engage properly.
Remove U-shaped knockout from top
3
center of housing. Hint: Use a pair of
wire cutters first to start a cut in the
thick portion at each side of the
knockout, then finish breaking it out
with pliers.
Cut
After knockout
removal