4.6.6.1
Electrical connection of the cooling unit
Fulfill the following general requirements to ensure safe and reliable operation of the cooling units:
•
Connection of an upstream temperature control on the feed side is prohibited.
•
Connect the upstream fuse specified on the type plate as line protection, see chapter "Type plate", Page 22and
"Adapting the unit to the mains voltage", Page 46.
•
Always connecting the cooling unit to the mains via a disconnecting device (switch/contactor).
–
The disconnecting device must have a 3 mm contact opening. The disconnecting device is provided and fitted by
the customer.
Fig. 22: Cooling unit mains plug
1
Cooling unit
2
Switch cabinet
3
Socket X51
(only on units with MC-Controller)
4
Socket X50
Operating Manual | Roof-mounted Cooling Unit | Standard Controller (SC) – 230 V | 086100022c
5
Ground connection
6
Coding pins
7
Plug
8
Screwdriver (flat, max. 3.5 mm)
9
Cable 0.5 to 2.5 mm²
G00059
45/46