Pfannenberg DTT 6401 Serie Manual De Instrucciones página 126

Ocultar thumbs Ver también para DTT 6401 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 274
ENG
Procedure
1.
Clean the evaporator fan (1) and condenser fan (2) with a soft brush, compressed air or a vacuum cleaner with a brush
attachment.
CAUTION – risk of injury. Do not touch the sharp heat exchanger fins.
CAUTION – dust development when cleaning with compressed air. Wear eye, mouth and nose protection when
cleaning with compressed air.
2.
Remove the condenser fan (2).
3.
Clean the heat exchanger (3) with a soft brush, compressed air or a vacuum cleaner with a brush attachment.
CAUTION – risk of injury. Do not touch the sharp heat exchanger fins.
CAUTION – dust development when cleaning with compressed air. Wear eye, mouth and nose protection when
cleaning with compressed air.
4.
Check the heat exchanger (3) for bent fins; align fins with a fin comb.
5.
Re-install the condenser fan (2).
6.
Remount the unit cover and front flap.
7.
Check that the cooling unit works properly and safely after cleaning.
The heat exchanger is cleaned.
Operating Manual | Roof-mounted Cooling Unit | Standard Controller (SC) – 230 V | 086100022c
58/59

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dtt 6101 serieDtt 6201 serieDtt 6801 serieDtt 6301 serie

Tabla de contenido