Siemens RDH100RF/SET Instrucciones De Funcionamiento página 6

Ocultar thumbs Ver también para RDH100RF/SET:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 13
DE
Front View Receiver
EN
LED Signal Indicator
FR
The signal is good when the
LED flashes green.
A flashing red LED indicates
IT
that there is no signal.
NL
ES
PT
CS
Rear View Room
HU
Unit
(Transmitter)
PL
SV
FI
ZH
Learn Button
Press and then release to
TR
learn telegram
Press > 5 s to enter
EL
parameter mode
RO
Configuration instructions for the Siemens RDH100RF/SET
DA
The transmitter RDH100RF and the receiver RCR100/433 are set to communicate (bonded) with each
other at the factory. If they fail it is necessary to re-bond the units due to the loss of communication,
please follow the below instructions.
1. Reset receiver by simultaneously pressing the LEARN & OVERRIDE button for 4 seconds.
2. Press and release the LEARN button. This sets the receiver to the learn mode.
3. Press and release the LEARN button on the back of the transmitter.
4. A green flashing or solid LED indicates a good signal, a red flashing or solid LED indicates no
signal.
5. To test transmission, press the TEST button on the transmitter, switches the relay on in
the receiver regardless of temperature. The RF TEST symbol appears on the thermostat display.
6. An orange LED indicates that the relay is on.
A6V101035988_en--_d
LED Relay Indicator
Orange LED indicates relay is on.
OVERRIDE Button
Press this button to overwrite transmitter
values.
RESET: Press the LEARN & OVERRIDE
button for 4 seconds to delete all transmitter
addresses.
LEARN Button
Press the button to learn a transmitter
address.
TEST Button
Used for testing transmission.
2018-06-21
Subject to alteration
NOTE:
You can press the OVERRIDE button on the receiver to manually switch ON/OFF for a faulty room unit
or transmission protocol.
NOTE:
You must re-execute the workflow for commissioning the set to reestablish a connection between the
room controller and receiver.
Parameter setting
Parameter setting mode
1.
Press LEARN on the rear for 5 seconds until "P01" appears.
2.
Press LEARN again and the parameter value on second line flashes
and is ready for adjustment.
3.
Adjust the parameter using setting knob.
4.
Press LEARN once to confirm the setting.
5.
Rotate the setting knob clockwise to next parameter and repeat steps 2
to 4.
6.
Exit parameter setting mode by rotating the setting knob clockwise to
"End" and pressing LEARN button once.
Parameters:
·
P01 Control behaviour: 2-position 1K / 2-position 0.5 K / PID fast / PID
slow (factory-setting)
·
P02 Maximum temperature range
·
P03 Minimum temperature range
Siemens Building Technologies / HVAC Products

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido