CERTIFIED APPLICATIONS
• Shower Version
WRAS Approval No: 160505D
NSF Certificate No: BC1777/1216 (renewal applied for)
• Certified Applications:
H9741TP SECURITHERM Securitouch thermostatic shower valve with thermal insulation
and Ergo control knob
• Complies with the NHS Model Specification DO8, designation HP-S and LP-SE when
operated as set out in Table below.
Operating Pressure Range
Maximum pressure - bar
Flow Pressure, Hot and Cold - bar
Hot Water Supply Temperature -°C
Cold Water Supply Temperature - °C
Mixed Water Temperature - °C
GENERAL FEATURES & TECHNICAL INFORMATION
General Features:
In the event of a sudden loss of the cold water supply, the hot water supply will be cut-off (response time
is 1 - 2 seconds) if the mixed water temperature selected is less than 42°C and the temperature differential
between the hot water and the mixed water is more than 15°C. Filters and non-return valves at the mixer
inlets protect the thermostat and prevent any back-flow into the pipework system.
Note: If, instead of cold water, the hot water returns through the mechanical mixer, there is no anti-scald
fail safe. We recommend installing a non-return valve on the cold water inlet of the mechanical mixer.
Technical Information:
• The factory pre-set is 38°C, with a temperature differential of 50°C between the cold and hot water.
• Range of mixed water settings: from 25°C to 40°C for H9739 and H9739S, and from 25°C to 41°C
for H9741, H9741S, H9741TP and H9752S. The maximum temperature limiter is set at 38°C
for H9739, H9739S and H9741TP. Models H9741, H9741S, and H9752S can be set at 41°C
by pressing on the button on the control knob , (Fig. C).
• Maximum hot water temperature: 85°C.
• Min./max. pressure: 1 - 5 bar (recommended 3 bar). Difference in pressure at water entry point:
maximum 1 bar.
• Safety: hot water shut-off in the case of loss of cold water. The hot water fail-safe is active
if the difference in temperature between the hot water and the cold water is more than 15°C.
• Flow rate regulated at 9 lpm.
• Temperature adjustment control is on the left and the flow-rate control is on the right.
INSTALLATION (Fig. A and B)
2 off-set connectors enable adjustable pipe-centres (150mm +/-20).
Mixers supplied with standard connectors:
1. Using PTFE or a waterproof sealant on the ½" threaded connector , tighten offset connectors
at right angles to the wall. Ensure a waterproof seal between the supply pipes and the finished wall.
2. Mount the offset connectors ensuring that the mixer is horizontal. Tighten the cover plates
onto the offset connectors by hand.
High Pressure Systems
10
1 to 5
55 to 65
5 to 20
41
Low Pressure Systems
10
0.2 to 1
55 to 65
5 to 20
41