PERIODIC TESTING
Article 700 of the National Electrical Code® states, "Systems shall be tested
periodically on a schedule acceptable to the authority having jurisdiction to
assure their maintenance in proper operating condition. " Also, "A written record
shall be kept of such tests and maintenance. "
In the absence of periodic testing requirements by a local authority, the following
recommendations from the NFPA 101 (2003) Life Safety Code are strongly
recommended:
1.
Monthly: Visually inspect the charging indicator light. It should be
illuminated when AC power is applied. Momentarily operate push-to-test
switch. Observe that emergency lighting fixtures are on full brightness
for the entire test cycle. Record the test on the Maintenance Record Card
(provided on next page).
2.
Annually: Shut off AC power at the distribution panel. Verify that the
emergency lighting fixtures remain "ON" for a minimum of 1-1/2 hours.
NOTE: We suggest that this test be continued until the power supply
automatically shuts the emergency light(s) off. This will help maintain full battery
capacity.
Record the test on the Maintenance Record Card.
Allow 24 hours charging time before depending on the battery to operate at full
capacity.
Failure to function properly in either test may indicate the need for EM driver
replacement.
CLEANING
The housing and lens may be washed with water and small amount of mild
detergent. Consideration should be given to use a non-abrasive type sponge
or cloth to clean the lens and avoid scratches. Wipe or rinse clean with fresh
water.
GENERAL
It should be noted that all components replaced must be in accordance with the
manufacturer's specifications. Failure to do so may invalidate the certification
and warranty of the fixture and could make the product dangerous. No
modifications should be made to fixture without the knowledge and consent of
the manufacturer. We reserve the right to make design changes without notice.
Copies of conditions of sale and warranty policy are available upon request. All
data is for guidance only.
IF 1836 • 10/17
ADDENDUM
Exposure to the following products may potentially cause damage or
discoloration to the LEDs.
1.
2.
3.
4.
5.
6.
7 .
8.
9.
10. Gasoline
11.
12. Dichloromethane
13. Tetrachloromethane
14. Some oils (castor, lard, linseed, silicone, vegetable)
15. Petroleum
16. Halogenated hydrocarbons (containing F , Cl, Br)
17 .
18. Loctite products (Sumo Glue, 384 Adhesive, 7387 Activator, 242
19. Clorox products (bleach, clean-up cleaner spray)
Copyright © 2017, Eaton's Crouse-Hinds Division
!
ATTENTION
Acids (Hydrochloric, Sulfuric, Nitric, Acetic)
Hydroxides (Sodium, Potassium)
Ammonia
Ketones (MEK (Methyl Ethyl), MIBK (Methyl Isobutyl))
Acetates (Methyl, Ethyl (nail polish remover))
Cyanoacrylates (Gorilla Glue (e.g. super glue))
Glycol ethers
Toluene/Xylene/Benzene
Formaldehyde/Butadiene
Mineral spirits
Rosin flux
threadlocker)
Page 3

Publicidad

Tabla de contenido
loading

Tabla de contenido