Descargar Imprimir esta página
Eaton Crouse-Hinds VMV Serie Información Para Instalación Y Mantenimiento
Eaton Crouse-Hinds VMV Serie Información Para Instalación Y Mantenimiento

Eaton Crouse-Hinds VMV Serie Información Para Instalación Y Mantenimiento

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

CHAMP HID Luminaires
VMV Series 50 - 175 Watts
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Champ® VMV series luminaires are suitable for use in the following
hazardous (classified) areas as defined by the National Electrical
Code (NEC®), Canadian Electrical Code (CEC), and International
Electrotechnical Commission (IEC):
• Class I Division 2 Groups A, B, C, D; Class I Zone 2 II
• Class I Zone 2, AEx nR II, Ex xR II
• IEC Zone 2, Ex nR II
• Class II Groups E, F & G; Simultaneaous Presence;
• Class III
WArNING
To avoid the risk of fire, explosion, or electric shock, this product
should be installed, inspected, and maintained by a qualified
electrician only, in accordance with all applicable electrical codes.
WArNING
To avoid electric shock:
Be certain electrical power is OFF before and during
installation and maintenance.
Luminaire must be supplied by a wiring system with an
equipment grounding conductor.
To avoid burning hands:
Make sure globe or refractor and lamp are cool when
performing maintenance.
INsTALLATION
Mounting
1. Mount the cover module in its support position.
Ceiling and Wall mount: Mark and drill desired location on
mounting surface. Secure with 1/4" bolts or lag screws (not
provided).
Pendant, Stanchion and Quad mount: Securely thread onto the
appropriate NPT size conduit. Tighten setscrew located in the
conduit hub. See figure 1.
Open
Hinge
Set Screw
Ground Wires
fIGure 1
Wiring
1.
Pull field wiring into cover module.
2.
Close all unused conduit entries with conduit plugs provided. To
prevent galling, lubricate conduit plugs with Cooper Crouse-Hinds
HTL lubricant before installing. Tighten plugs securely with at least
five full threads engaged.
3.
Hang ballast housing on the cover module
hinge hook. See figure 2.
4.
Connect supply wires to luminaire wire
leads (or terminals) per the attached wiring
diagrams using methods that comply with
all applicable codes. See figure 2. Tighten
all electrical connections.
fIGure 2
WArNING
To avoid explosion: On ballasts with multiple supply voltage
taps (MT, TT, MV, etc), all unused leads must be capped with
closed end wire connectors.
For MH PS 175W luminaire perform visual check that
insulation material is present on both sides of the ballast
bracket. See figure 2a
IF 1108 • 10/14
Copyright © 2014, Eaton's Crouse-Hinds Business
IF 1108
Refer to the luminaire nameplate for specific classification information,
maximum ambient temperature suitability and corresponding operating
temperature (T-Code).
VMV series luminaire 4X / IP66 construction is designed for use
indoors and outdoors in Marine and Wet locations, where moisture,
dirt, corrosion, vibration and rough usage may be present. VMV series
luminaires are supplied with a choice of voltages (120, 208, 220, 240,
277, 480, tri-tap, multi-tap, etc.) and light sources, High Pressure Sodium
(HPS), Metal Halide (MH), Mercury Vapor (MV), in ratings of 50 through
175 watts.
WArNING
To avoid explosion:
Make sure the supply voltage is the same as the luminaire
voltage.
Do not install where the marked operating temperatures
exceed the ignition temperature of the hazardous
atmosphere.
Do not operate in ambient temperatures above those
indicated on the luminaire nameplate.
Install luminaire with lamp base up within 25º of vertical.
Use only the lamp and wattage specified on the luminaire
nameplate.
Use proper supply wiring as specified on the luminaire
nameplate.
All gasket seals must be clean.
Before opening, electrical power to the luminaire must be
turned off. Keep tightly closed when in operation.
Insulation
fIGure 2a
5.
Close ballast housing onto cover module making sure that all wires
are safely inside and positioned away from the ballast area. Tighten
captive closing screw to 30 in.-lbs (3.4 N-m).
6.
Install lamp as specified on the nameplate. See LAMP
INSTALLATION AND REPLACEMENT section.
7.
Install globe or refractor and optional guard and reflector. See the
instructions that follow.
8.
Turn power on.
GLObe ANd GuArd INsTALLATION
1. VMV Champ® series luminaire globe
cat. no. G24 use an integral guard
cat. no. P21.
Thread segments of
both guard and globe are of unequal
length (keyed) to insure proper globe
and guard thread match upon assembly.
The clip that is attached to the guard
helps to secure the guard to the globe.
See figure 3.
2. To assemble, align correctly, then push
globe and guard together.
fIGure 3
3. Apply a small amount of HTL® Lubricant
to the threads of globe and guard.
4. Thread the globe and guard assembly as a unit into the ballast
housing. Hand tighten securely.
refrACTOr INsTALLATION
1. Install refractor on luminaire by placing over lamp and hand tighten
onto ballast housing.
2. Follow the instruction furnished with refractor for complete installation
and adjustment information.
3. R and PR type refractors are not marine suitable.
4. Compact refractors, G241 and G245, are marine suitable.
refLeCTOr INsTALLATION
1. Install dome or angle reflector by placing the keyway slots over the
mounting studs on the ballast housing and rotating clockwise until it
"snaps" into position.
LAMP INsTALLATION ANd rePLACeMeNT
1.
Disconnect power to luminaire and allow to cool completely.
2. Remove globe or refractor and the guard if used.
3. Remove lamp.
4. Perform cleaning and inspection as noted in the MAINTENANCE
section.
5. Screw new lamp into lampholder and hand tighten securely. New
lamp must be identical type, size and wattage as marked on the
luminaire nameplate.
6. Thoroughly clean or replace the globe gasket seal.
7. Apply a small amount of HTL® Lubricant to the threads of the globe
and guard (if used) or refractor.
8. Thread the globe and guard (if used) and refractor into the ballast
housing and hand tighten securely. Refer to the GLOBE AND GUARD
INSTALLATION or REFRACTOR INSTALLATION section above for
more information.
CAuTION
To prevent ballast damage on high pressure sodium
luminaires, replace burned out lamps as soon as possible.
To avoid shortened lamp life, lampholder failure,
wiring faults or ballast failure, secure lamp firmly and
completely.
To avoid injury, guard against lamp breakage.
MAINTeNANCe
• Perform visual, electrical, and mechanical inspections on a regular
basis. The environment and frequency of use should determine this.
However, it is recommended that checks be made at least once a
year. We recommend an Electrical Preventive Maintenance Program
as described in the National Fire Protection Association Bulletin
NFPA No. 70B: Recommended Practice For Electrical Equipment
Maintenance (www.nfpa.org).
• The globe/refractor (and guard and reflector when used) should be
cleaned periodically to insure continued lighting performance. To
clean, wipe the reflector, then the globe with a clean damp cloth.
If this is not sufficient, use a mild soap or a liquid cleaner such as
Collinite NCF or Duco #7. Do not use an abrasive, strong alkaline, or
acid cleaner. Damage may result.
• Visually check for undue heating evidenced by discoloration of wires
or other components, damaged parts, or leakage
water or corrosion in the interior. Replace all worn, damaged, or
malfunctioning components and clean gasket seals before putting the
luminaire back into service.
• Electrically check to make sure that all connections are clean and
tight.
• Mechanically check that all parts are properly assembled.
rePLACeMeNT PArTs
Crouse-Hinds VMV Series Champ Luminaires are designed to provide
years of reliable lighting performance. However, should the need for
replacement parts arise, they are available through your authorized
Crouse-Hinds distributor. Assistance may also be obtained through your
local Crouse-Hinds representative or theEaton's Crouse-Hinds Sales
Service Department, P.O. Box 4999, Syracuse, New York 13221, Phone
315/477-7000.
WIrING dIAGrAMs
Mercury Vapor (MV) - 100 and 175 watts
All Voltages
Metal Halide (MH) -
175 watts
All Voltages
All statements, technical information and recommendations contained herein are based on information and tests we believe to be
reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale",
and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use
and assumes all risk and liability whatsoever in connection therewith.
Page 1
High Pressure sodium (HPs) - 50, 70, 100 and 150 watss (LX)
High Pressure sodium (HPs) -
50, 70, 100 and 150 watts
208, 240, 277 and 480V
High Pressure sodium (HPs) - 150 watt (Ce)
evidenced by
rapid restrike Option - 50, 70, 100 and 150 watts (LX)
HPs Only (Catalog suffix Ir)
fIeLd AsseMbLed fIXTures
Champ® VMV series Lighting fixtures, 50-175 watts.
Complete lighting fixture consists of cover, ballast enclosure
and globe or refractor, with or without guard or refractor.
Eaton's Crouse-Hinds Business
1201 Wolf Street, Syracuse, New York 13208 • USA
Copyright © 2014
120V only
Metal Halide (MH) - 70, 100 watts
120, 208, 240, 277 and 480V
120, 208, 240, 277 (MT) and 480V
IF 1108
Revision 8
Revised 10/14
Supersedes 11/10

Publicidad

loading

Resumen de contenidos para Eaton Crouse-Hinds VMV Serie

  • Página 1 See figure 2a Eaton’s Crouse-Hinds Business IF 1108 1201 Wolf Street, Syracuse, New York 13208 • USA Revision 8 Copyright © 2014 Revised 10/14 IF 1108 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 1 Supersedes 11/10...
  • Página 2 Eaton’s Crouse-Hinds Business IF 1108 le sens des aiguilles d’une montre jusqu’à ce qu’il “s’enclenche” en 1201 Wolf Street, Syracuse, New York 13208 • USA Revision 8 position. Copyright © 2014 Revised 10/14 IF 1108 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 3 Supersedes 11/10...
  • Página 3 1. Desconecte el suministro de energía y espere que enfríe la luminaria completamente. 1201 Wolf Street, Syracuse, New York 13208 • USA Revision 8 2. Retire el bombillo o refractor y la guarda si tiene. Copyright © 2014 Revised 10/14 IF 1108 • 10/14 Copyright © 2014, Eaton’s Crouse-Hinds Business Page 5 Supersedes 11/10...