Desert-cooler: DCP30; DCP30 Top4
Use only motors of the same size, dimensions and shape as the original motor.
Following the motor mounting, give power to the electric panel only after having closed all the protections
and only after this verify the sequence of the phases by turning on the motor.

Pump substitution

• Verify that the machine is not hooked up to the power line.
• Disconnect the pump cable from the electric panel.
• Unscrew the tank plug and drain the water.
• Remove the pump cover.
• Remove the fixing strips from the spiral pipe.
• Remove the intake and outtake pipes from the pump.
• Unfasten the four bolts that hold the pump to the metal support and remove the pump.
• Invert this procedure to install the new pump.

Substitution of evaporative media

For the DCP30 model follow these steps:
• Verify that the machine is not hooked up to the power line.
• Remove the fastening screws from the top, and then remove the top.
• Remove the fastening screws from the splash guards, and then remove the splash guards.
• Remove the perforated water distribution pipes.
• Access the CELdek panels and remove them.
• Position the new CELdek panels making sure to align them correctly according to the paper wrap.
• Invert this procedure to re-install perforated pipes, the splash guards and the top.
For the DCP30 Top4 model follow these steps:
• Verify that the machine is not hooked up to the power line.
• Remove the air distribution tower from the upper part of the machine.
• Remove the fastening screw from the top, and then remove the top.
• Remove the fastening screws from the splash guards, and then remove the splash guards.
• Remove the perforated water distribution pipes.
• Access the evaporative media panels and remove them.
• Position the new evaporative media panels making sure to align them correctly according to the paper
wrap.
• Invert this procedure to re-install perforated pipes, the splash guards and the top.

Lubrication

No periodic lubrication is necessary since all the moving parts are self lubricating or sealed.

Substitution of electric panel components

• Verify that the machine is not hooked up to the power line.
• Open the electric panel by unfastening the 4 screws.
• Inside the panel, locate the component that has to be substituted.