ADJUST SETPOINT AT THE DESIRED VALUE BY ACTUATING SELECTOR.
INLET PRESSURE (MAXIMUM): 250 PSI
REDUCED PRESSURE RANGE:
25 TO 90PSI 3/4 IN. TO 1-1/4 IN. SIZE
NOTE: DO NOT DISMANTLE
KNOB
SET-POINT READOUT HAS BEEN
CALIBRATED IN THE FACTORY AND SET
AT 60 PSI. DISMANTLING THE SELECTOR KNOB
WILL CANCEL THIS CALIBRATION. RECALIBRATE
USING A PRESSURE GAUGE. SEE RECALIBRATION.
Fig. 2. Changing outlet pressure.
MAINTENANCE
We recommend a planned maintenance contract with an
installation company.
Inspection
Filter
Frequency: at least every 2 month (depending on local
operating conditions.
• Non-compliance can lead to the filter becoming blocked
This results in a drop in pressure and decreasing water
flow
• The filter meshes are made of stainless steel. A red
coating as a consequence of rust from the pipelines has
no influence on function or the way the filter works
To be carried out by an installation company or the operator.
NOTES:
Filtered water can be drawn during rinsing.
If rinsing is into a container, then a suitable con-
tainer must first be put underneath.
1. Open the ball valve by turning the rinse knob. Rinse
knob must be vertical.
2. Close the ball valve after approximately 15 seconds.
NOTE:
A longer rinse period may be necessary if the
filter is very dirty (Replace filter mesh see
Maintenance)
LOOSEN LOCKING
SCREW ONE TURN
M36657A
3
15s
2
Fig. 3. Rinsing the filter.

Pressure reducing valve

Replacing the Cartridge (Fig. 4)
The working parts of the FK06, including diaphragm, valve
seat, strainer, and disk are all contained in a replaceable
cartridge. To replace the cartridge:
1. Close shutoff valve on inlet.
2. Release pressure on outlet side (e.g. through water
tap).
3. Close shutoff valve on outlet.
4. Loosen slotted screw (do not remove the screw).
CAUTION
To prevent injury and/or equipment damage, loosen
locknut and turn adjusting screw counter-clockwise
to remove spring tension.
5. Slacken tension in compression spring by turning
counter clockwise until it does not move anymore.
6. Unscrew Bonnet.
7. Remove slip ring.
8. Remove cartridge using a pliers as a lever.
9. Reassemble bonnet in reverse order.
Recalibrate
If the dial knob assembly has been disassembled
recalibration is necessary.
1. Close shutoff valve on inlet.
2. Release pressure on outlet side (e.g. through water
tap).
3. Close shutoff valve on outlet.
4. Remove dust cap.
5. Loosen slotted screw (do not remove screw).
6. Fit pressure gauge.
7. Slowly open shutoff valve on inlet.
8. Set desired outlet pressure (e.g. 60 psi).
9. Align scale (e.g. 60 psi) in middle of viewing window.
10. Re-tighten slotted screw.
11. Slowly open shutoff valve on outlet.
BRAUKMANN FK06 DIALSET®
1
M36610A
38-00059EFS—05