1 Overview

This product is an 8 Input/8 Output device that allows the ACTpro controller       t o be used in applications 
where signalling to other equipment is required.         E xamples of this are elevator control, alarm systems,        
CCTV switching and general monitoring.
A maximum of 4 Input/Output Modules may be connected to any single controller,       g iving control of up to 32 
relays and 32 inputs per ACT4000/ACT1520.
See also:
 
http://van.fyi?Link=ACTproIOM
l

1.1 Features

 
8 form C relays
l
 
8 supervised inputs
l
 
Tamper protection
l
 
3 status LEDs
l
 
Timer for each output
l
 
Input timer
l
 
Output switched ON/OFF by log event, input or timezone
l
 
ACTEnterprise support
l

1.2 ACTEnterprise support

 
Named inputs and outputs
l
 
Inputs and outputs Logged
l
 
Normally open/closed
l
 
Active on timezone
l
 
Active on event, user, door or user group
l
 
Active on input on/off
l
 
Active on output on/off
l

1.3 Technical specification

Voltage
Current Consumption
Communications
Operating Temperature
Mounting
Installation
Weight
Dimensions
© Vanderbilt 2018
12V DC
250mA
RS485 to ACTpro controller
-10°C to +50°C / +14°F to +122°F
Surface
Indoors
500g / 1.102lb
236mm wide, 165mm high, 55mm deep / 9¼" wide x 6½" high x 2¼" deep