6. EXTERNAL UNIT INSTALLATION
Aluminised tape
Refrigeration piping
Indoor unit condensation drain
Electrical connection cable
between the units
- Provide to use a protection sheet for the cables exposed to the outside.
- It is recommended to set the cables with a drip-proof run in order to
avoid possible infiltrations of water in the outdoor unit.
- Combine the electrical connection cable of the two units to the refrigera-
tion piping and wrap with reinforced tape, possibly alluminized (Fig. C).
- If the cable cannot be solid with the piping, make a suitable wall ancho-
rage by means of a cable fastener or hose clips..
6.4.4
Connection to the outdoor unit terminal board
- Remove the two fixing screws and take off the terminal board cover as
shown in fig. D, E, F.
- Connect the cable to the terminal block as shown Fig. G
Single Hi-Wall
Fig. D
Dual Hi-Wall
Fig. E
52
Trial Hi-Wall
Fig. C
Fig. F
- Loosen the screws and insert the ends of the cable completely into the
terminal block, after this tighten the screws.
Fig. G
- Pull the cable lightly to make sure that the cables have been insert and
fixed rightly.
- After cables connection never forget to tight them to the cable gland.
GB
GB
70 mm
10 mm
10 mm
50 mm