Temperature and leakage relay type ABS CA 462, Installation guide
EN
4
TECHNICAL DATA
4.1 Technical data CA 462
Leakage detection threshold (±10%)
Temperature input threshold (±10%)
Leakage alarm delay
Ambient operating temperature
Ambient storage temperature
Degree of protection
Housing material
Mounting
Installation category
Pollution degree
Flame rate
Humidity
Dimensions
Power supply
Fuse
Terminal wire size
Terminal tightening torque
Power consumption
Max load alarm relays
Altitude
Max load output pump blocking relay
Compliance
Attention
If the unit is used in a manner not described in this document the protection
provided by the equipment may be impaired.
4.2 Cleaning
How to clean the unit
Powers off the unit and only outside/front shall be cleaned by using a dry, soft
cloth. A good choice would be the microfiber type of cloth and gently wipe the
CA 462 unit on front in order not to scratch the overlay. If the dry cloth did not
completely remove the dirt, do not press harder in an attempt to scrub it off. If
necessary, moisten the cloth by adding a small amount of water with thin solution
of mild detergent and try again. Never use detergent with polish or solvent which
can have an impact of the plastic surface.
< 100 kohm
> 3.3 kohm (PTC / Klixon)
10 seconds
–20 to +70 °C (–4 to +158 °F)
–30 to +80 °C (–22 to +176 °F)
IP 20, NEMA: Type1
PPO and PC
DIN Rail 35 mm
CAT II
2
V0 (E45329)
0–95% RH non-condensing
H x W x D: 108 x 70 x 58 mm
(4.25 x 2.76 x 2.28 inch)
16907006
110-230 VAC
16907007
18-36 VDC SELV or Class 2
Max 10 A
Use copper (Cu) wire only. 0.2 - 2.5 mm
flexible core, stripped length 8 mm.
0.56 - 0.79 Nm (5 -7 lbs-in)
< 5 W
250 VAC 3 Ampere resistive load
Max 2000 MASL or 6562 ft. AMSL
250 VAC 6 Ampere resistive load
6
2