Important Safety Instructions & Guidelines
Risk of Breathing
Risk of
Electrical
Shock
Risk of
Explosion
or Fire
Risk of Bursting
Avoid
using the air compressor
in confined
areas. Always
have adequate
space
(12 inches) on all sides of the air compressor. Also keep children, pets, and others out
of the area of operation. This air compressor does not provide breathable air for anyone
or any auxiliary breathing device. Spraying material will always need to be in another
area away from the air compressor to not allow intake air to damage the air compressor
Never utilize the air compressor
in the rain or wet conditions.
Any electrical
issues
or repairs should be performed
by authorized
personnel such as an electrician
and
should comply with all national and local electrical codes. The air compressor should
also have the proper three prong grounding plug, correct voltage, and adequate fuse
protection.
Never operate the compressor near combustible
materials, gasoline or solvent vapors.
If spraying flammable
materials, locate the air compressor at least 20 feet away from
the spray area. Never operate the air compressor indoors or in a confined area.
Always drain the air compressor tank daily or after each use. If the tank develops a leak,
then replace the air compressor.
Never use the air compressor
after a leak has been
found or try to make any modifications
to the tank. Never modify the air compressor's
factory settings which control the tank pressure or any other function.
Specifications
Pump .........................
Oil-Free Direct Drive
Motor ....................................
1.5 HP
Bore .......................................
2.28"
Stroke ......................................
0.87"
Voltage Single Phase ......................
120 VAC
Glossary
CFM:
Cubic feet per minute.
SCFM: Standard cubic feet per minute; a unit of measure
for air delivery.
PSIG:
Pounds per square inch gauge; a unit of measure
for pressure.
ASME: American Society of Mechanical Engineers.
California
Code: Unit may comply with California Code
462 (I) (2)/(M) (2).
Duty Cycle
Minimum Circuit Requirement ..............
15.0 Amps
Air Tank Capacity ........................
20 Gallons
Cut-in Pressure ...........................
120 PSI
Cut-out Pressure ..........................
150 PSI
SCFM @ 90 PSI ...............................
3.8
SCFM @ 40 PSI ...............................
5.1
Cut-In Pressure:
The air compressor will automatically
start to refill the tank when the pressure drops
below the prescribed minimum.
Cut-Out Pressure: The point at which the motor stops
when the tank has reached maximum air
pressure.
Code Certification:
Products that bear one or more of
the following marks: UL, ULc, ETL, CSA, have
been evaluated by OSHA-certified
independent
safety laboratories and meet the applicable
Underwriters
Laboratories Standards for Safety.
This is a 50% duty cycle air compressor.
Do not run the air compressor more than 30 minutes of one hour. Doing so
could damage the air compressor.