Technical Data - SFA SANICONDENS Clim Classic Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 5
UK
1. Box contents
SANICONDENS Clim Classic
Pump unit
4
Triple-level sensor
4
1
1: pump
2: level sensor
2a: lid
2b: float ball
2c: filter
2d: reservoir
2e: stopper
3: pipe 1.2m, Øint 4.6mm
4: vent connection.
2. Warning notice
SANICONDENS Clim Classic
Designed only for pumping water.
4
State-of-the-art electrical installation.
4
Must not run dry.
4
Install all level sensors horizontally.
4
Install indoors only (domestic or indus-
4
trial premises).

3. Technical data

Sound level at 1 m
23 dB(A)
Maxi. flow rate
13.5 l/h
Maxi. horizontal discharge
12 m
Maximum vertical
5 m
discharge
Maximum air vent length
2 m
Electricity supply
220-240V - 50-60Hz
Power
22 W
Trips at 80°C and then
Thermal protection
automatically resets
Maximum temperature
35°C
of water
4. Installation
A – Level Sensor unit
4
Magnet facing upwards.
4
Cover on.
4
Connect the short pipe (150mm)
to the lid vent, point it upwards
and secure.
Fit the level sensor horizontally.
4
B – Pump unit
Install the pump in the trunking
1
4
Make sure the the pump is pointing in the right direction (see arrows on the pump
unit).
4
Install the pump vertically (preferably).
Make sure there is enough room around the pump unit for it to cool off in the
4
event of prolonged usage.
4
Ensure that electrical connections are not exposed to water.
SANICONDENS Clim Classic is guaranteed for two years subject to correct installation and usage (*).
comprises two components:
2a
4
3
2
Do not submerge.
4
Unplug the appliance prior to
4
maintenance.
Point the float ball with the magnet
4
upwards
Height in metres
16
14
12
10
8
6
4
2
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
or in the suspended ceiling
.
2
2
1
SANICONDENS Clim Classic
2c
2b
C – Hydraulic connections
2e
Feed the incoming condensate to the level sensor inlet 1 .
4
Connect the pump and the level sensor up using the pipe supplied 2 .
4
Evacuation 3 :
4
2d
The pump outlet must be connected to the waste water discharge
using a suitable fitting with an inner diameter of 8 to 10mm
(not supplied).
!
Warning: To prevent siphoning, the discharge outlet must be
higher than the condensate tank.
D – Electric connections
Connect the level sensor to the pump unit using the cable.
4
Litres per hour
Electricity supply:
4
Plug the pump in (phase, earth, neutral):
• either by way of the air conditioner
• or directly using a 30-mA circuit breaker.
5. Start-up
4
Check pumping direction
(see arrow on the pump unit).
Introduce water into the level sensor.
4
4
Check that the pump starts up and then stops
once the water level has dropped.
4
Check that the connections are all waterproof.
6. Maintenance
Maintenance must only be carried out with the appliance switched off.
4
This product must be maintained at the start of each summer season, or regularly if
4
the pump is used year round.
Clean:
4
• the reservoir,
• the filter,
• the float ball.
• Replace all items and close the reservoir.
SFA
1
2
*
3
2

Publicidad

Tabla de contenido
loading

Tabla de contenido