Suggested Installation Equipment (not supplied with kit)
Cable preparation tools
Tyco Electronics P63 cable preparation kit or cable manufacturer
approved solvent
Clean, lint-free cloths
Non-conducting abrasive cloth, 120 grit or finer
Electrician's tape
Connector(s) and installation tools
Tyco Electronics recommended torch
Safety Instructions
DANGER: When installing electrical power system accessories,
failure to follow applicable personal safety requirements and written
installation instructions could result in fire or explosion and serious
or fatal injuries.
To avoid risk of accidental fire or explosion when using gas torches,
always check all connections for leaks before igniting the torch and
follow the torch manufacturer's safety instructions.
To minimize any effect of fumes produced during installation, always
provide good ventilation of confined work spaces.
As Tyco Electronics has no control over field conditions which
influence product installation, it is understood that the user must
take this into account and apply his own experience and expertise
when installing product.
Cleaning the Cable
Use an approved solvent, such as the one supplied in the P63 Cable
Prep Kit, to clean the cable. Be sure to follow the manufacturer's
instructions. Failure to follow these instructions could lead to
product failure.
Some newer solvents do not evaporate quickly and need to be
removed with a clean, lint-free cloth. Failure to do so could change
the volume resistivity of the substrate or leave a residue on the
surface. Please follow the manufacturer's instructions carefully.
PII 51081
Revision AE
MCK-xV
1000V Flame-Retarded Motor (Stub) Connection Kits for
1/C Low-Voltage Power Cable
Recommended Tyco Electronics Torches
Install heat-shrinkable cable accessories with a "clean burning" torch,
i.e., a propane torch that does not deposit conductive contaminants
on the product.
Clean burning torches include the Tyco Electronics FH-2629,
FH-2649 (uses refillable propane cylinders) and FH-2618A (uses
disposable cylinder).
Adjusting the Torch
Adjust regulator and torch as required to provide an overall 12- inch
bushy flame. The FH-2629 will be all blue, the other torches will have
a 3- to 4-inch yellow tip. Use the yellow tip for shrinking.
Regulator Pressure
FH-2618A
Full pressure
FH-2649
25 psig
FH-2629
15 psig
General Shrinking Instructions
Apply outer 3- to 4-inch tip of the flame to heat-shrinkable material
with a rapid brushing motion
Keep flame moving to avoid scorching
Unless otherwise instructed, start shrinking tube at center,
working flame around all sides of the tube to apply uniform heat
To determine if a tube has completely recovered, look for the following,
especially on the back and underside of the tube:
1. Uniform wall thickness
2. Conformance to substrate
3. No flat spots or chill marks
4. Visible sealant flow if the tube is coated
Note: When installing multiple tubes, make sure that the surface of
the last tube is still warm before positioning and shrinking the next
tube. If installed tube has cooled, re-heat the entire surface.
Customer Service
For 24 hour customer service, call 800-327-6996.
1
PCN 043944-000
Effective Date: August 13, 2009

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Tyco Electronics MCK-V Serie

  • Página 1 • Keep flame moving to avoid scorching As Tyco Electronics has no control over field conditions which • Unless otherwise instructed, start shrinking tube at center, influence product installation, it is understood that the user must...
  • Página 2: Installation Instructions

    Installation Instructions 1. Product selection Check kit selection with cable dimensions in Table 1. Table 1 Motor Feeder Bolt Length Connection Length Conductor Size Max (D) Max (H) MCK-1V #14-#10 AWG 5/8” (15mm) 2.0” (50mm) MCK-2V #12-#4 AWG 3/4” (20mm) 2.5”...
  • Página 3 However, Tyco Electronics Corporation has no control over the field conditions which influence product installation. It is the user’s responsibility to determine the suitability of the installation method in the user’s field conditions. Tyco Electronics’ only obligations are those in Tyco Electronics’ standard Conditions of Sale for this product and in no case will Tyco Electronics be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products.
  • Página 4: Ajustando El Soplete

    A menos que se instruya de hacerlo distinto, comience a termocontraer el tubo desde el centro, trabajando la flama alrededor de todas las Los sopletes de flama limpia incluyen al Tyco Electronics FH-2629 partes del tubo para aplicar un calor uniforme. Para determinar si el (usa cilindros de propano recargables) y FH-2616A1 (usa cilindros tubo se ha instalado correctamente obsérvelo especialmente en la...
  • Página 5: Instructivo De Instalación

    Instructivo de Instalación 1. Selección del Producto Verique la selección del kit con las dimensiones del cable en la Tabla 1. Tabla 1 Longitud de Calibre Longitud tornillo la Conexión Alimentador Max (D) Max (H) MCK-1V #14-#10 AWG 5/8” (15mm) 2.0”...
  • Página 6 Es la responsabilidad del usuario determinar el método de instalación apropiado de acuerdo con las condiciones de campo en las que estará el instalador. Las únicas obligaciones de Tyco Electronics son aquellas que se encuentran en las condiciones estándar de venta de Tyco Electronics para este producto, y en ningún caso Tyco Electronics será...

Este manual también es adecuado para:

Mck-3vMck-5-1vMck-5-2vMck-4v

Tabla de contenido