Tyco Electronics CRSM Serie Guia De Inicio Rapido

Manga abierta de reparación

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Safety Instructions
When installing electrical power system accessories,
failure to follow applicable personal safety
requirements and written installation instructions could result in fire
or explosion and serious or fatal injuries.
To avoid risk of accidental fire or explosion when
using gas torches, always check all connections for
leaks before igniting the torch and follow the torch manufacturer's
safety instructions.
To minimize any effect of fumes produced during
installation, always provide good ventilation of
confined work spaces.
As Tyco Electronics has no control over field
conditions which influence product installation, it is
understood that the user must take this into account and apply his
own experience and expertise when installing product.
Working around energized high-voltage systems may
cause serious injury or death. Installation should
be performed by personnel familiar with good safety practice in
handling high-voltage electrical equipment. De-energize and ground
all electrical systems before installing product.
Power distribution and transmission products must
be properly selected for the intended application. It
must be installed and serviced by competent personnel who have
been trained and understand proper safety procedures. These
instructions are written for such personnel and are not a substitute
for adequate training and experience in safety procedures.
Read and understand the contents of these
instructions before installation and follow all locally
approved procedures and safety practices before installing or
operating this equipment
These instructions cannot cover all details or variations
in the equipment, procedures, or processes described,
nor provide directions for meeting every possible contingency during
installation, operation, or maintenance. When additional information
is desired to satisfy a problem not covered sufficiently for the user's
purpose, please contact your Tyco Electronics sales representative.
These instructions are not intended to supersede or replace existing
safety and operating procedures.
Upon receipt of a product, inspect it thoroughly for
damage and loss of parts incurred during shipment.
If damage or loss is discovered, file a claim with the carrier
immediately or contact your Tyco Electronics representative.
PII 51068
Revision AD
CRSM Cable Repair
Sleeve
Insulation Repair on 1/C Solid Dielectric Cables to 1kV
& Outer Jacket Sheath Repair on all Cables
Suggested Installation Equipment (not supplied with kit)
• Cable preparation tools
• Tyco Electronics P63 cable preparation kit or cable manufacturer
approved solvent
• Clean, lint-free cloths
• Non-conducting abrasive cloth, 120 grit or finer
• Electrician's tape
• Connector(s) and installation tools
• Tyco Electronics recommended torch
Recommended Tyco Electronics Torches
Install heat-shrinkable cable accessories with a "clean burning" torch,
i.e., a propane torch that does not deposit conductive contaminants
on the product.
Clean burning torches include the Tyco Electronics FH-2629,
FH-2649 (uses refillable propane cylinders) and FH-2618A (uses
disposable cylinder).
Adjusting the Torch
Adjust regulator and torch as required to provide an overall 12- inch
bushy flame. The FH-2629 will be all blue, the other torches will have
a 3- to 4-inch yellow tip. Use the yellow tip for shrinking.
Regulator Pressure
FH-2618A
Full pressure
FH-2649
25 psig
FH-2629
15 psig
General Shrinking Instructions
• Apply outer 3- to 4-inch tip of the flame to heat-shrinkable material
with a rapid brushing motion
• Keep flame moving to avoid scorching
• Unless otherwise instructed, start shrinking tube at center,
working flame around all sides of the tube to apply uniform heat
To determine if a tube has completely recovered, look for the follow-
ing, especially on the back and underside of the tube:
1. Uniform wall thickness
2. Conformance to substrate
3. No flat spots or chill marks
4. Visible sealant flow if the tube is coated
When installing multiple tubes, make sure that the
surface of the last tube is still warm before positioning
and shrinking the next tube. If installed tube has cooled, re-heat the
entire surface.
Customer Service
For 24 hour customer service, call 800-327-6996.
1
PCN 121979-000
Effective Date: October 19, 2010

Publicidad

loading

Resumen de contenidos para Tyco Electronics CRSM Serie

  • Página 1 When installing electrical power system accessories, • Cable preparation tools failure to follow applicable personal safety • Tyco Electronics P63 cable preparation kit or cable manufacturer requirements and written installation instructions could result in fire approved solvent or explosion and serious or fatal injuries.
  • Página 2: Installation Instructions

    Installation Instructions 1. Product selection Check kit selection with cable diameter dimension in Tables 1 & 2. Table 1: Primary Insulation on1/C Solid Dielectric Cable to 1kV Nominal Cable Range Diameter Range CRSM-34/10 #8-2/0 0.25-0.60” (6-15mm) CRSM-53/13 3/0-400 0.60-0.95” (15-24mm) CRSM-84/20 500-1000 0.95-1.40”...
  • Página 3 However, Tyco Electronics Corporation has no control over the field conditions which influence product installation. It is the user’s responsibility to determine the suitability of the installation method in the user’s field conditions. Tyco Electronics’ only obligations are those in Tyco Electronics’ standard Conditions of Sale for this product and in no case will Tyco Electronics be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products.
  • Página 4: Crsm Manga Abierta De Reparación

    3. Sin puntos planos o marcas frías por favor, contacte con su representante de ventas de Tyco Electronics. 4. Flujo sellador visible en el tubo Estas instrucciones no pretenden suplantar o reemplazar de seguridad existentes y los procedimientos operativos.
  • Página 5 Installation Instructions 1. Selección de Producto Verifique la selección del kit con las dimensiones de diámetro en las Tablas 1 y 2. Tabla 1: Aislamiento Primario en el Cable con Dieléctrico Sólido 1/C a 1kV Calibre Nominal Rango de Diámetro CRSM-34/10 #8-2/0 0.25-0.60”...
  • Página 6 Es la responsabilidad del usuario determinar el método de instalación apropiado de acuerdo con las condiciones de campo en las que estará el instalador. Las únicas obligaciones de Tyco Electronics son aquellas que se encuentran en las condiciones estándar de venta de Tyco Electronics para este producto, y en ningún caso Tyco Electronics será...

Este manual también es adecuado para:

Crsm-34/10Crsm-53/13Crsm-84/20Crsm-107/29Crsm-143/36Crsm-198/55