Operation
RECEPTACLES
CAUTION
NEVER attempt to power a device requiring more
amperage than generator or receptacle can supply.
DO NOT overload the generator. See "Don't Overload
Generator';
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14-30 plug with this receptacle.
Connect a 4-wire cord set rated for 250 Volt AC loads
at 30 Amps (or greater) (Figure 8). You can use the
same 4-wire cord if you plan to run a 120 Volt load.
4-Wire Cord Set
/
\
(Neutral)
IIIIII
h._¢_° _
Y (Hot)
X (Hot)
NEMA L14-30
f-_
Ground
(Green)
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 6,500 watts of power
(6.5 kW) at 27 Amps for 120 Volts or 240 Volts. The
outlet is protected by a push-to-reset
circuit breaker.
iMPORTANT: This generator's locking receptacle is
not protected by a Ground Fault Circuit Interrupter
(GFCI). If used on an OSHA governed job site,
appropriate GFCI protection must be utilized.
120 Volt AC, 20 Amp, GFCI Duplex
Receptacles
Each duplex receptacle (Figure 9) is protected against
overload by a push-to-reset
circuit breaker.
Use each receptacle to operate 120 Volt AC,
single-phase,
60 Hz electrical loads requiring up to
2,400 watts (2.4 kW) at 20 Amps of current. Use cord
sets that are rated for 125 Volt AC loads at 20 Amps
(or greater).
12 Volt DC, 10 Amp Receptacle
This receptacle (Figure 10) allows you to recharge a
12 Volt automotive or utility style storage battery with
the battery charge cables provided.
This receptacle can not recharge 6 Volt batteries and
can not be used to crank an engine having a
discharged battery. See "Charging a Battery" on
page 11 before attempting to recharge a battery. This
outlet is protected by a 10 Amp self-resetting circuit
breaker.
O