INSTALLATION
3.
NOTE For Zone 4, it is recommended to use 5/16" self-drill bolts and hardware with
1 5/16" minimum embedment for 3000PSI-strength concrete. Refer to your local building
codes for seismic mounting requirements.
18
Avaya EBC240 Site Preparation, Installation and Operator's Manual
5/16" Bolts
Figure 1. Seismic Installation Mounting Plates
A seismic installation of the EBC240 requires that the mounting
plates be bolted to the floor. See Figure 2 for a detailed drill and
mounting pattern.
Mounting Plate
S
164201531 Rev C