5.input/output configuration
Switch off device
• Take the front face off.
• Select input and output calibres using the straps
as indicated on the right.
• Connect the instrument to a < 0.2 accuracy
rating multimeter
Switch on device
Input x V / x A
• Generate 0 V / A
• Set output down scale, using potentiometer P1
• Generate full scale on the input
• Set output full scale using potentiometer P2
• Adjust down and full scale settings if necessary
Symetrical input : ± xmV / ± xmA
• Apply 0 mV / mA
• Adjust the half scale of the output thanks to the
potentiometer P1 (eg : 5V if 0-10V, 0mA if ±20mA)
• Apply the full scale at the input
• Adjust the full scale of the output thanks to the
potentiometer P2
• Readjust the half and full scales if nedeed.
• Check the down scale in applying the down scale
of the input.
Note :
For any configurations not mentionned above,
please consult with us for a feasability study.
C -Output configuration
View of board with
front face taken off
Configuration
OUTPUT
Down scale
setting
Full scale
setting
Configuration
INPUT
p5
A -DC current input configuration
B -DC voltage input configuration
Your instrument is now ready to work.