1
Electrical connection
Pos. Description
1
Protective earth terminal
2
Neutral terminal
3
Phase terminal
40mm (1.58")
30mm (1.18")
Wire requirements
Related information
6. Electrical connection
6.3 Connecting GENIbus to the pump
6.5 Connecting the IO connections
10
2
3
N
L
5mm
(0.20")
N
L
5mm
(0.20")

6.3 Connecting GENIbus to the pump

1. Remove the front cover.
2. Lead the GENIbus cable through the cable gland.
3. Connect the conductors to terminals A, Y and B.
4. Connect the cable screen under the earth clamp,
and tighten the earth clamp.
5. Tighten the cable gland.
6. Fit the front cover.
Example:
1
2
A
Y
GENIbus connection
Pos.
Designation Description
GENIbus terminal A. Positive
1
A
data signal.
2
Y
GENIbus terminal Y
GENIbus terminal B.
3
B
Negative data signal.
4
-
Earth clamp
Related information