Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Operating voltage
Loop consumption
Standby
Alarm
Frequency
IP rating
Operating temperature
Storage temperature
Relative humidity
(noncondensing)
Dimensions
Sound pressure level
Sounder Pressure Level values vary depending on the angle
and distance of the user from the siren. The following table
indicates SPL values at a distance of 1 metre on the horizontal
plane using an operating voltage of 36 V.
Angle
15°
45°
75°
105°
135°
165°
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
Declaration of Performance
number [1]
Year of first CE marking
Product identification
Intended use
Essential characteristics
2 / 12
21 to 36 V
300 µA
max. 5 mA
1 Khz
IP21C
−10°C to +50°C
−10°C to +70°C
10% to 95%
58 x Ø 120 mm
SPL value (min.)
75 dB(A)
73 dB(A)
77 dB(A)
77 dB(A)
73 dB(A)
75 dB(A)
0370
360-4109-1799
07
KZ715AS
See the product Declaration of
Performance
See the product Declaration of
Performance
Manufacturer
[1] This device has been tested and certified using shielded 1.5 mm²
twisted-pair cable.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS. UTC
FIRE & SECURITY CANNOT PROVIDE ANY ASSURANCE
THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS,
INCLUDING ANY "AUTHORIZED DEALER" OR
"AUTHORIZED RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code:
P/N 10-4221-501-3KZA-04 • ISS 18JUN20
United Technologies Safety
System Co. Ltd., 80, Changjiang
East Road, QETDZ,
Qinhuangdao, Hebei Province,
China 066004
Authorized EU manufacturing
representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert,
Netherlands
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For
more information see:
www.recyclethis.info.

Publicidad

loading