Descargar Imprimir esta página

Lutron EcoSystem C5-BMJ-16A Manual Del Usuario página 2

Ocultar thumbs Ver también para EcoSystem C5-BMJ-16A:

Publicidad

Idiomas disponibles

Idiomas disponibles

EcoSystem
Power Module Junction Box Mount | Install Guide
TM
Step 1: Determine Mounting Location for Module
EcoSystem Power Modules must be mounted onto a
4 in. x 4 in. standard (1900) junction box (not included,
but available - Lutron Part Number 241-296). Follow
applicable local and national codes.
NOTE: The wire length between the dimming module
and the ballast it is controlling shall not exceed
500 feet (152 m).
Mount the module indoors with ambient temperature
o
between 32
F and 104
ty < 90% (non-condensing).
DO NOT INSTALL WHILE ENERGIZED.
Do not connect any electrically live circuits to the
module prior to installation.
5 in.
(130 mm)
7.8 in.
(150 mm)
The module can be mounted on vertical or horizontal
surfaces (i.e. ceiling). Mount in a location where the
PWR and STAT indicators are visable.
W
A
L
L
EcoSystem Power Module Wiring
Distribution
Panel
Ground
Neutral
Live
2 | Lutron
®
o
o
o
F (0
C and 40
C) and humidi-
2.5 in.
(64 mm)
CEILING
Green
Green (Ground)
White
White (Neutral)
Black
Red (Switched Hot)
Orange (Dimmed Hot) - C5-BMJ-16A
CLASS 2 LOW VOL
T AGE WIRING
www.lutron.com/ecosystem
Step 2: Wire Power Module to Mains and Loads
Live and neutral from a distribution panel is required
to power the module.
Lighting loads must match the selected input volt-
age. Verify that 120 V~ loads are used only with
120 V~ mains, and 277 V~ loads are used only with
277 V~ mains. DO NOT use different voltage loads
on the same control circuit.
D D i i m m m m i i n n g g P P o o w w e e r r M M o o d d u u l l e e
Three wires are used between the BMJ and a
Hi-lume or Eco-10 ballast. The wires are color coded
as follows:
C5-BMJ-16A
RED
ORANGE
WHITE
GREEN
S S w w i i t t c c h h i i n n g g P P o o w w e e r r M M o o d d u u l l e e
Two wires are used between the XPJ and non-dim
loads. The wires are color coded as follows:
C5-XPJ-16A
RED
WHITE
GREEN
Module can support up to 16 A of attached switched
load current.
Use the following steps to wire a module to
mains and ballast(s).
A.
DO NOT WIRE LIVE. Interrupt power via breaker
before wiring between the module and a ballast.
B. Connect mains feed wires and output wires to the
Power Module as shown in the diagram below.
N N o o t t e e : : Colors indicated are for
wires coming out of the module
Green
White
Black
Orange
Green
White
Black
To Additional Loads
Lutron World Headquarters: +1-610-282-3800
Ballast
BLACK
Switched Hot
ORANGE
Dimmed Hot
WHITE
Neutral
GREEN
Ground
Load
BLACK
Switched Hot
WHITE
Neutral
GREEN
Ground
* * See additional ballast installation
guides for wire and terminal require-
ments.
Fixture Ground
Lutron FDB or ECO
Dimming Ballast
Fixture Ground
Non-Dim Load