Power Module Junction Box Mount | Install Guide
TM
Step 3: Mounting the Module
A.
Using two screws from the junction box, attach the
module to the junction box.
B. Be sure all power wires are completely inside the
junction box before tightening the mounting screws.
C. Turn on breaker to energize the module.
D. Attached ballast(s) or loads will turn on to full light
output.
Hz
~
50 /60
V
27 7
10 0–
Ma x.
16 A
O N
O N
LU TR
LU TR
ICA TO
R
it has
R IND
n un
PO WE
On :
Ca utio
r
po we
g
ctio nin
Off : is no t fun
rly
pro pe
gh t
gh t
Da yli
Da yli
or
Se ns
N N O O T T E E : : If lamp(s) do not turn on, verify that the power
(PWR) indicator LED is on. (STAT) indicator will blink if
no communication is present.
Step 4: Wire EcoSystem Bus
The EcoSystem Bus Supply controls up to 64 ballasts
and ballast modules. EcoSystem Bus wiring may be run
daisy chain, t-tap, and/or star pattern.
Bus wiring may be either Class 1 or Class 2.
• Class 1: Low voltage bus wiring may be run with
mains voltage to any fixture the bus is controlling.
N N O O T T E E : : I I f f w w i i r r e e d d C C l l a a s s s s 1 1 , , a a l l l l C C l l a a s s s s 2 2 m m a a r r k k i i n n g g s s m m u u s s t t b b e e
r r e e m m o o v v e e d d f f r r o o m m t t h h e e l l i i n n k k s s e e c c t t i i o o n n o o f f t t h h e e p p r r o o d d u u c c t t . . F F o o r r m m o o r r e e
i i n n f f o o r r m m a a t t i i o o n n , , p p l l e e a a s s e e r r e e a a d d A A p p p p l l i i c c a a t t i i o o n n N N o o t t e e # # 1 1 4 4 2 2
( ( w w w w w w . . l l u u t t r r o o n n . . c c o o m m / / a a p p p p l l i i c c a a t t i i o o n n n n o o t t e e s s ) ) . .
• Class 2: Low voltage bus wiring must be separated
from all mains and Class 1 wiring.
Consult all applicable national and local codes for com-
pliance.
Lutron recommends using two different colors for E1
and E2 (EcoSystem Bus) wire. This helps prevent bus
wiring mistakes.
Use the following guidelines for wiring the
EcoSystem Bus to the module.
A.
DO NOT WIRE LIVE. Interrupt power to the module and
the EcoSystem Bus Supply before wiring and/or servic-
ing the EcoSystem Bus.
B. Connect EcoSystem Bus wires E1 and E2 to module
terminals E1 and E2.
C. Energize the EcoSystem Bus Supply only. Verify that
18 V
is present at the E1 and E2 terminals on the
module.
D. Energize the module.
E.
If there is no power/communication on the link, the sta-
tus (STAT) LED will blink once per second.
Technical Support: +1-800-523-9466
Wiring Size and Bus Length
Step 5: Wire Sensor Inputs
24 hours/7 days
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
C5-BMJ-16A
Power Indicator (PWR)
Indicador de Alimentación (PWR)
Indicateur de puissance (PWR)
On: Unit is powered
On: l'unité est alimentée
Encendido: unidad tiene corriente
Off: Unit is not powered
Off: l'unité n'est pas alimentée
Apagado: unidad no tiene corriente
or is malfunctioning
o no está funcionando correctamente
ou est dysfonctionnelle
Status Indicator (STAT)
Indicateur d'activité (STAT)
Indicador de estado (STAT)
Solid: Circuit Level
Plein: Niveau de circuit
Sólido: Nivel del Circuito
Pulse: No communication
Impulsion: Aucune
Pulsante: No hay comunicación
communication
EcoSystem
TM
Class 2 Sensors
Class 2 Link
Capteurs Classe 2
Lien Classe 2
PWR
STAT
Sensores Clase 2
Enlace Clase 2
E1
E2
E1 - Purple
E2 - Purple/White
EcoSystem Bus length is limited by the wire gauge
used for E1 and E2 as follows:
Wire Gauge
#12 AWG (3.30 mm
)
2
#14 AWG (2.09 mm
2
)
#16 AWG (1.31 mm
)
2
#18 AWG (0.82 mm
2
)
If sensors are wired to the module follow these
guidelines.
Refer to sensor specifications for proper wire gauge
and maximum wire distances between the sensor
and the module.
All sensors and wallstations are Class 2 low volt-
age. Do not combine any sensor wiring with mains
wiring.
Follow all national and local electrical code
restrictions when wiring Class 2 devices.
Wire sensors as instructed by each sensor's
instruction sheets.
Programming of each sensor and wallstation is
performed via the EcoSystem Programmer
(C-PDA-CLR)
Power Module can power only 1 of each type of
sensor (occupancy, IR, and daylight).
...see next page for wiring diagrams
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
C5-BMJ-16A
Power Indicator (PWR)
Indicador de Alimentación (PWR)
Indicateur de puissance (PWR)
On: Unit is powered
On: l'unité est alimentée
Encendido: unidad tiene corriente
Off: Unit is not powered
Off: l'unité n'est pas alimentée
Apagado: unidad no tiene corriente
or is malfunctioning
o no está funcionando correctamente
ou est dysfonctionnelle
Status Indicator (STAT)
Indicateur d'activité (STAT)
Indicador de estado (STAT)
Solid: Circuit Level
Plein: Niveau de circuit
Sólido: Nivel del Circuito
Pulse: No communication
Impulsion: Aucune
Pulsante: No hay comunicación
communication
EcoSystem
TM
Class 2 Sensors
Class 2 Link
Capteurs Classe 2
Lien Classe 2
PWR
STAT
Sensores Clase 2
Enlace Clase 2
E1
E2
To additional
EcoSystem
modules, ballasts,
and the
EcoSystem Bus
supply
Bus Length (max)
2,200 ft. (671 m)
1,400 ft. (427 m)
900 ft. (275 m)
570 ft. (175 m)
Lutron
| 3
®