Technical Data
6.1
Technical data SP-SCOP1 / SC-COP2-xxx
SP-COP2-xxx
Safety Integrity Level
SIL3 (IEC 61508)
SIL claim limit
SILCL3 (EN 62061)
Category
Category 4 (EN ISO 13849-1)
Performance Level (PL)
PL e (EN ISO 13849-1)
PFHd (average probabil-
see BA000966, Sec. Safety Specific
ity of dangerous failure
Characteristics
per hour)
Mission time T
20 years (EN ISO 13849)
M
Protection class
III (EN 61140)
Protection degree
IP 20 (EN 60529)
Ambient temperature in
–25 °C ... +65 °C
operation
Storage temperature
–25 °C ... +70 °C
Humidity
10 % ... 95 %, non condensed
Vibration according
5 Hz ... 150 Hz, (EN 60068-2-6)
Shock proof
- continuous shock
10 g, 16 ms (EN 60068-2-29)
- single shock
30 g, 11 ms (EN 60068-2-27)
Electromagnetic Compa-
Class A (EN 61000-6-2, EN 55011)
tibility
System connector
Internal safety bus
Configuration Bus 1
USB-Mini-B
Configuration Bus 2
Ethernet-RJ 45 (SP-COP2-ENx only)
Dimensions (W x H x D)
- Screw terminal
45 x 96,5 x 121 mm
- Spring terminal
45 x 107 x 121 mm
Weight
290 g (± 5 %)
Terminals and connec-
Screw type
tion data
terminals
Single-core or finely
1 x 0,2–2,5 mm
stranded
2 x 0,2–1,0 mm
Finely stranded with
1 × 0,25–2,5 mm²
wire-end ferrule acc. to
2 × 0,25–1,0 mm²
DIN 46228
AWG (use Cu lines only) 26–14
Max. tightening torque
0.5–0.6 Nm
(5-7 lbf-in)
Single-core or finely
1 × 0.2–1.5 mm²
stranded
Stripping length
7 mm
Power Supply (A1, A2)
Supply voltage
24 V DC (16,8 ... 30 V DC)
Type of power supply
PELV or SELV
With an external current limitation of 4 A
by the power supply or with a fuse.
Power consumption
Max. 3,3 W
Attention: the power
consumption is in-
creased with every
connected module.
ON-Delay
max. 18 s
Short-circuit protection
4 A gG
Power Supply B1 and B2 (B2: only SP-COP2)
Supply voltage
24 V DC (16,8 ... 30 V DC)
Type of power supply
PELV or SELV
With an external current limitation of 8 A
per output group (B1 and B2) by the
power supply or with a fuse.
Power consumption
2 x 0,3 W
Short circuit protection
8 A gG
12
Spring type
terminals
2
2 x 0,2–1,5 mm²
2
2 x 0,25–1,5 mm²
24–16
̶
Input circuit
SP-COP1: (I1 ... I20)
SP-COP2-xxx: I1 - I16, IQ1 - IQ4
Number of Inputs:
SP-COP1
20
SP-COP2-xxx
20 (16 inputs fix, 4 inputs selectable)
Input voltage HIGH
13 ... 30 V DC
Input voltage LOW
–5 ... +5 V DC
Input current HIGH
Typ 2.3 mA / Max. 6 mA
Input current LOW
< 2 mA
Input capacity
10 nF
Reverse current input at
< 0,1 mA
measurement interrupt
Test output (T1 - T4)
Number of outputs
4 (with 4 groups of independent test
pulses)
Type of output
PNP-semiconductor, push-pull, short-
circuit proofed
Output voltage HIGH
U
Output current LOW
-10 mA (limited)
Output current HIGH
Single output: max. 120 mA;
sum of all testpulse outputs: max.
120 mA
Testpulse frequency
1 Hz ... 25 Hz, configurable
Testpulse duration
1 ms ... 100 ms, configurable
Load capacity
1 µF for testpulse duration ≥ 4 ms
0,22 µF for testpulse duration 1 ms
< 100 Ω
Resistance
Safety output:
SP-COP1: Q1 - Q4
SP-COP2-xxx: Q1 - Q4, IQ1 - IQ4
Number of outputs:
SP-COP1
4
SP-COP2-xxx
8 (4 outputs fix, 4 outputs selectable)
Type of output
High-Side-MOSFET, short-circuit
proofed, current controlled
Output voltage High
U
Output current High
≤ 4,0 A
Max. overload current /
≤ 12 A / 8 ms
period
Sum current Isum
Each output pair (Q1/2, Q3/4, IQ1/2,
IQ3/4)
≤ 45 °C
T
≤ 4,0 A
U
≤ 55 °C
T
≤ 2,5 A
U
≤ 65 °C
T
≤ 1,6 A
U
Output test,
deactivatable
Test pulse
≤ 450 µs
Test pulse rate
10 Hz
Leakage current Low
< 0,1 mA
Load capacity
0,5 µF
< 200 Ω
Line resistance
Max. allowed coil energy
< 0,125 J
without external protec-
tion
Reaction time
Depends on logic extension
6.2
Approvals
TUEV
UL: The safety functions are not evaluated by UL. The approval is
accomplished according to UL 508, general use applications.
- 1,2 V
A1
≥ U
- 0,6 V
Qn
Bx