contacting the fence with the head, mouth, neck or torso. Do not climb
over, through or under a multi-wire electric fence. Use a gate or a specially
designed crossing point.
• An electric animal fence shall not be supplied from two separate energizers or from independent
fence circuits of the same energizer.
• For any two separate electric animal fences, each supplied from a separate energizer independently
timed, the distance between the wires of the two electric animal fences shall be at least 2.5m. If
this gap is to be closed, this shall be effected by means of electrically non-conductive material or an
isolated metal barrier.
• Barbed wire or razor wire shall not be electrified by an energizer.
• A non-electrified fence incorporating barbed wire or razor wire may be used to support one or more
off-set electrified wires of an electric animal fence. The supporting devices for the electrified wires
shall be constructed so as to ensure that these wires are positioned at a minimum distance of 150
mm from the vertical plane of the non-electrified wires. The barbed wire and razor wire shall be
earthed at regular intervals.
• Follow the energizer manufacturer's recommendations regarding earthing.
• A distance of at least 10 m shall be maintained between the energizer earth electrode and any
other earthing system connected parts such as the power supply system protective earth or the
telecommunication system earth.
• Connecting leads that are run inside buildings shall be effectively insulated from the earthed
structural parts of the building. This may be achieved by using insulated high voltage cable.
• Connecting leads that are run underground shall be run in conduit of insulating material or else
insulated high voltage lead-out cable shall be used. Care must be taken to avoid damage to the
connecting leads due to the effects of animal hooves or tractor wheels sinking into the ground.
• Connecting leads shall not be installed in the same conduit as the mains supply wiring,
communication cables or data cables.
• Connecting leads and electric animal fence wires shall not cross above overhead power or
communication lines.
• Crossings with overhead power lines shall be avoided wherever possible. If such a crossing cannot be
avoided it shall be made underneath the power line and as nearly as possible at right angles to it.
• If connecting leads and electric animal fence wires are installed near an overhead power line, the
clearances shall not be less than those shown in the table below.
Minimum clearances from power lines for electric animal fences
Less than or equal to 1 000
Greater than 1 000 and less than or equal to 33 000
Greater than 33 000
• If connecting leads and electric animal fence wires are installed near an overhead power line, their
height above the ground shall not exceed 3 m.
6
Power line Voltage V
3E3888 Gallagher S400 Solar Energizer User Manual
Clearance m
3
4
8