CONNECTIONS – Detection circuit
A shielded cable must be used: connect the shield of the cable (one end in a loop mode) to the ground
in the control panel only and connect the shield between a device.
The section of leads can vary according to the length of the detection line.
A lead section of 1,5 mm
Don't use cable that exceed these limits:
Maximum resistance: 100 Ω
Maximum capacitance: 2µF
The electrical connection must be performed by removing approximately 10 mm of insulating cover from
the main lead and insert it on the terminal block.
DETECTION
CIRCUIT
INPUT
-
+
SH
-
+
SH
DETECTION
CIRCUIT
OUTPUT
Detection circuit connection
The IO501 module is only to be used with ELKRON FAP series Control Panels.
2
is advised.