SHUTTING THE GENERATOR OFF
1.
Remove entire electrical load.
2.
Let the engine run for a few minutes without load.
3.
Move the engine switch (C) to the off "STOP" position.
4.
Do not leave the generator until it has completely stopped.
5.
If a cover is used, do not install until unit has cooled.
APPLYING LOAD
This unit has been pretested and adjusted to handle its full
capacity. When starting the generator, disconnect all load.
Apply load only after the generator is running. The voltage is
regulated via the engine speed adjusted at the factory for the
correct output. Readjusting is not advised.
CAUTION: When applying a load, do not
exceed the maximum wattage rating of the
generator when using one or more
receptacles. Also, do not exceed the
amperage rating of any one receptacle.
MAJOR FEATURES
AC FEATURES
The Pulse Series generators are equipped with two 120-
volt receptacles (A). The total wattage of the generator may be
drawn from either receptacle.
Use only good quality, well insulated grounded cord sets to
plug into the generator receptacles. Make sure the wire gauge
of the cord set is sufficient to handle the amount of current
listed on the electrical load's nameplate.
For example: A cord set comprised of 14 AWG wire is
capable of handling up to 15 amps of current at 120 volts.
CAUTION: Do not exceed the generator's
rated wattage and/or amperage capacity for
continuous operation. Damage to the
generator or equipment may result.
NOTE: Electrical - The ampacity of the phase conductors
from the generator terminals to the first over current device
shall not be less than 115 percent of the nameplate rating of
the generator.
AC CIRCUIT BREAKER
The AC circuit is protected by a thermal circuit breaker. A
receptacle overload or an external short-circuit will cause the
AC breaker to trip, thereby protecting the unit. If this occurs,
disconnect all electrical loads and reset the circuit by pushing in
on the button head (B). (You may need to wait a few seconds
for the circuit breaker to cool before it will reset.)
6
Before reapplying the load, determine why the breaker
tripped by referring to the trouble shooting chart introduced
later in the manual. Correct the problem and reapply the load
to the generator.
DC FEATURES
BATTERY CHARGER:
NOT RECOMMENDED FOR USE WITH GEL PACK,
SEALED, OR SMALL (MOTORCYCLE) BATTERIES.
These generators contain an additional circuit used for
battery charging purposes. A two-prong DC receptacle (D) is
provided on the control panel. A battery charging cable
equipped with a matching plug for this receptacle has been
supplied with the unit.
The battery charger on this generator is referred to as an
unregulated taper charger - the most widely used in the market
today. The amount of current flowing will depend on the
charging voltage and battery's state of charge. As the battery
becomes more fully charged, the output current to the battery
decreases and nearly becomes constant. Taper chargers are
intended to be used with the provision that they will be
disconnected from the battery after a maximum time on charge.
Normally a period of 30 to 120 minutes is sufficient to recharge
a weak battery. The charge level of the battery should be
checked periodically.
CAUTION: This battery charging system is
intended to recharge weak batteries, not to
"boost start" vehicles.
Note: When the battery charger circuit is in use, the AC
capacity is reduced by 180 watts. Make sure the combined
load is within the rated limits.
Before charging a storage battery, check the electrolyte
fluid level in all the cells. (Sealed batteries do not require
checking.) Add distilled water to each cell, if necessary, to
bring the level back up to the manufacturer's required level.
WARNING: Storage batteries give off
EXPLOSIVE hydrogen gas while charging. Do
not allow smoking, open flames, sparks, or
spark producing equipment in the area while
charging.
Connect the red clip to the positive terminal of the battery.
Connect the black clip to the negative terminal of the battery.
Insert the DC plug into the DC receptacle of the generator.
After the battery is fully charged, remove the battery charging
cable from the generator and then disconnect from the battery
posts.
WARNING: Battery electrolyte fluid is
comprised of sulfuric acid that can be very
dangerous and cause severe burns. Do not
allow this fluid to contact eyes, skin, clothing,
etc. If contact or spillage does occur, flush
the area with water immediately.
DC CIRCUIT BREAKER: The maximum current available
from the battery charger circuit is 15 amps. An automatic DC
circuit breaker has been provided to protect the circuit from
overloads and assure that the battery gets recharged. If an
overload occurs, the circuit breaker will trip. After it cools, it will
automatically reset itself. The battery's maximum rate of
charge will eventually reduce to less than 15 amps and then to
zero as the battery approaches a 100 percent state of charge.
English