3.2 User parameter editing
Sliding Temperature - Compensation curve
By installing the external probe (optional) the control system is able to work
with Sliding Temperature. The external probe must be connected to the boiler
board: see the relevant manual. In this mode the heating system temperature
is adjusted according to the outside weather conditions, in order to ensure high
comfort and energy saving throughout the year. In particular, as the outside
temperature increases, the system flow temperature decreases according
to a specific compensation curve. With Sliding Temperature adjustment,
the temperature set via the "Heating temperature adjustment" becomes
the maximum system flow temperature. It is advisable to set a maximum
value to allow system adjustment throughout its useful operating range.
The compensation curve can be adjusted from 1 to 10 according to the
following graph.
By adjusting the curve to 0 the Sliding Temperature is disabled.
The system must be adjusted during installation by qualified personnel. The user can still make further adjustments for better comfort. If the room temperature is lower than the desired
value, it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the room.
1. Press the button
2. The display shows parameter CU.
3. Press any other button to exit the menu.
code 3541Z230 - Rev. 03 - 09/2021
External temperature
for 3 seconds.
Press the buttons
/
increments of 1 unit. By keeping the button pressed the value will change
rapidly.
to change the compensation curve in
EN