5 Unit installation
3 Insert a wall cover into the wall pipe.
a b
c
a
Wall embedded pipe
b
Putty
c
Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do
NOT forget to seal the gap with putty.
5.2.3

To remove the pipe port cover

INFORMATION
To connect the piping on right-side, right-bottom, left-side
or left-bottom, the pipe port cover MUST be removed.
1 Cut off the pipe port cover from inside the front grille using a
coping saw.
2 Remove any burrs along the cut section using a half round
needle file.
NOTICE
Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.
5.3

Connecting the drain piping

5.3.1
To connect the piping on right side, right-
back, or right-bottom
INFORMATION
The factory default is right-side piping. For left-side piping,
remove the piping from the right side and install it on the
left side.
1 Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.
2 Wrap the drain hose and the refrigerant pipes together using
insulation tape.
Installation manual
10
A
C
a b
B
A
Right-side piping
B
Right-bottom piping
C
Right-back piping
a
Remove the pipe port cover here for right side piping
b
Remove the pipe port cover here for right-bottom piping
5.3.2
To connect the piping on left side, left-
back, or left-bottom
INFORMATION
The factory default is right-side piping. For left-side piping,
remove the piping from the right side and install it on the
left side.
1 Remove the insulation fixing screw on the right side and
remove the drain hose.
2 Remove the drain plug on the left side and attach it to the right
side.
NOTICE
Do NOT apply lubricating oil (refrigerant oil) to the drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.
3 Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.
a
b
a
Insulation fixing screw
b
Drain hose
4 Attach the drain hose to the refrigerant piping bottom side using
adhesive vinyl tape.
b
A
Left-side piping
B
Left-back piping
C
Left-bottom piping
a
Remove the pipe port cover here for left-side piping
b
Remove the pipe port cover here for left-bottom piping
5.3.3

To check for water leaks

1 Remove the air filters.
a
b
a
A
B
C
FTXP-M + FTXF-D + FTXF-A + ATXF-A
Daikin room air conditioner
3P512025-10U – 2021.07