Connection
A heat block or check valve should be fitted in order to prevent convection (self-circulation) of hot water.
Three examples are shown below:
*)
b)
c)
a)
d)
a)
b)
d)
b)
Diagram
Pressure-drop
*)
kPa
30
20
TA-MIX installed over the boiler
To prevent back-flow and building up of pressure in the cold water line, connection
should be done as shown in the sketch.
a) Mixed water
b) Hot water
c) Cold water
d) Boiler
*) Shortest possible distance
TA-MIX installed beside the boiler
Install the TA-MIX about 0,75 - 1,0 m below the top of the boiler.
a) Mixed water
b) Hot water
c) Cold water
d) Boiler
c)
a)
Floor-mounted calorifier
a) Mixed water
b) Hot water
c) Cold water
c)
l/s**
*) mWG
**) Water flow in l/s
3