To display boiler operating information, proceed as follows:
•
Press
for approx. 6 seconds. When the function is enabled, the display shows "A00" (..."A07") alternating with the respective
( )
value (figure 13);
5 seconds
Figure 13
•
Press the +/- DHW temperature adjustment buttons (
A00:
instantaneous DHW temperature (°C);
A01:
instantaneous external temperature (°C) (with external probe connected);
A02:
current (%) at modulator (100% = 230 mA NATURAL GAS - 100% = 310 mA LPG);
A03:
power range (%) (MAX R) - Parameter F13 (section 21);
A04:
heating setpoint temperature (°C);
A05:
instantaneous heating delivery temperature (°C);
A06:
not used;
A07:
flame signal (8-100%).
NOTE:
display lines A08 and A09 are not used.
•
This function remains active for 3 minutes. To interrupt the "INFO" function, press
NOTE:
5 reset attempts can be performed after which the boiler shuts down. To make a new reset attempt, proceed as follows:
• press
selecting "OFF" (as described in section 3.2;
• press for about 2 seconds, the display shows "OFF";.
• reset the boiler operating mode.
Fault codes and descriptions are shown in section 9.
For more detailed technical information, please consult the "SERVICE INSTRUCTIONS".